TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■
EXTERNAL DIMENSIONS unit: mm (inch)
4 5 6
1 2 3
18 (0.71)
90 (3.54
)
6.5 (.26)
90 (3.54)
5.6 (.22
)
LOCKING CLAMP
POSITIONING GUIDE
■
CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG
terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
INTERNAL
POWER
1
2
4
5
INTERNAL
BUS
V
U
FG
POWER INPUT
RUN
+
RUN
–
RUN CONTACT OUTPUT
3
BUS CONNECTOR
■
WIRING INSTRUCTIONS
Applicable wire size: 0.2 to 2.5 mm
2
(AWG24 to 12)
Stripped length: 7 mm
(Tinning wire ends may cause contact failure and therefore
is not recommended.)
CURRENT CONSUMPTION
The network module and I/O modules operate with 24 V DC
power supply via the power supply module. The total cur-
rent consumption of the network module and I/O modules
is required to be not more than the continuance output cur-
rent (400 mA) of the power supply module. If the total cur-
rent consumption exceeds the capacity of the power supply
module, change the combination of I/O modules or reduce
the number of I/O modules.
MODEL NO.
MAX. CURRENT (mA)
R6x-SV2
20
R6x-SS2
20
R6x-TS2
20
R6x-TS2A
20
R6x-RS2
20
R6x-DS1
55
R6x-YV2
25
R6x-YS2
45
R6x-DA4
10
R6x-DC4A
20
R6x-DC4B
20
R6-NC1
110
R6-NC3
110
R6-ND1
40
R6-NE1
75
R6-NE2
75
R6-NM1
50
R6-NM2
50
R6-NF1
100
R6-NP1
100
RUN CONTACT OUTPUT
Terminals (4 – 5) turns on in normal communications with
the host PLC.
Terminals (4 – 5) turns off in an abnormal communication
status.