R6-PSM

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7781-BZ  Rev.2  P. 2 / 2

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

4 5 6

1 2 3

18 (0.71)

90 (3.54

)

6.5 (.26)

90 (3.54)

5.6 (.22

)

LOCKING CLAMP

POSITIONING GUIDE

 

CONNECTION DIAGRAM

Note:  In order to improve EMC performance, bond the FG 

terminal to ground.

Caution: FG terminal is NOT a protective conductor terminal.

INTERNAL

POWER 

1

2

4

5

INTERNAL

BUS 

V

U

FG

POWER INPUT

RUN

+

RUN

RUN CONTACT OUTPUT

3

BUS CONNECTOR

 

WIRING INSTRUCTIONS

Applicable wire size: 0.2 to 2.5 mm

2

 (AWG24 to 12)

Stripped length: 7 mm
(Tinning wire ends may cause contact failure and therefore 
is not recommended.)

CURRENT CONSUMPTION

The network module and I/O modules operate with 24 V DC 
power supply via the power supply module.  The total cur-
rent consumption of the network module and I/O modules 
is required to be not more than the continuance output cur-
rent (400 mA) of the power supply module.  If the total cur-
rent consumption exceeds the capacity of the power supply 
module, change the combination of I/O modules or reduce 
the number of I/O modules.

MODEL NO.

MAX. CURRENT (mA)

R6x-SV2

20

R6x-SS2

20

R6x-TS2

20

R6x-TS2A

20

R6x-RS2

20

R6x-DS1

55

R6x-YV2

25

R6x-YS2

45

R6x-DA4

10

R6x-DC4A

20

R6x-DC4B

20

R6-NC1

110

R6-NC3

110

R6-ND1

40

R6-NE1

75

R6-NE2

75

R6-NM1

50

R6-NM2

50

R6-NF1

100

R6-NP1

100

RUN CONTACT OUTPUT

Terminals (4 – 5) turns on in normal communications with 
the host PLC.
Terminals (4 – 5) turns off in an abnormal communication 
status.