background image

COMPONENT IDENTIFICATION

RUN Indicator LED

ERR Indicator LED

Configuration Jack

Euro Type

Connector Terminal

2

1

3

4

5

6

7

8

ON

■ 

SIDE VIEW

■ 

FRONT VIEW

ON

1 2 3 4 5 6 7 8

Node Address

Function

Data

Parity

Baud Rate

LED Function

Data Allocation

 

SIDE DIP SW

(*) Factory setting

• Data Allocation Mode: SW1, SW2 

SW

DATA ALLOCATION MODE

2

1

1

OFF (*)

ON

2

OFF (*)

OFF

• LED Function: SW3

SW3

LED FUNCTION

RUN

ERR

OFF (*) Green when normal

Green ON/blinks in an 
abnormality

ON

Red when receiving

Red when transmitting

• Baud Rate: SW4, SW5

SW

BAUD RATE (bps)

38.4k

19.2k

9600

4800

4

OFF

ON (*)

OFF

ON

5

OFF

OFF (*)

ON

ON

• Parity: SW6, SW7 

*

1

SW

PARITY

NONE

ODD

EVEN

N/A

6

OFF (*)

ON

OFF

ON

7

OFF (*)

OFF

ON

ON

• Data Mode: SW8

 *

1

SW

DATA MODE

RTU (Binary)

ASCII

8

OFF

ON (*)

*1. Bit assignment according to Parity and Data Mode setting

DATA MODE

START

DATA

PARITY

STOP

RTU

1

8

1

1

1

8

None

2

ASCII

1

7

1

1

1

7

 None

2

 

FRONT DIP SW

• Node Address

ADD.

DIP SW

1

2

3

4

5

6

7

8

1

ON

OFF OFF OFF OFF OFF OFF OFF

2

OFF

ON

OFF OFF OFF OFF OFF OFF

3

ON

ON

OFF OFF OFF OFF OFF OFF

4

OFF OFF

ON

OFF OFF OFF OFF OFF

5

ON

OFF

ON

OFF OFF OFF OFF OFF

6

OFF

ON

ON

OFF OFF OFF OFF OFF

7

ON

ON

ON

OFF OFF OFF OFF OFF

:

:

:

:

:

:

:

:

:

247

ON

ON

ON

OFF

ON

ON

ON

ON

PC CONFIGURATOR

With configurator software, settings shown below are available.
Refer to the software manual of R5CON for detailed operation.

 

NETWORK MODULE SETTING 

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Communication Timeout

0.0 – 3276.7 (sec.)

3.0 (sec.)

R5-NM1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-6104  Rev.8  P. 2 / 7

Содержание R5-NM1

Страница 1: ...nit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 10 to 55 C 14 to 131 F with relative humidity within 30 to 90 RH i...

Страница 2: ...MODE RTU Binary ASCII 8 OFF ON 1 Bit assignment according to Parity and Data Mode setting DATA MODE START DATA PARITY STOP RTU 1 8 1 1 1 8 None 2 ASCII 1 7 1 1 1 7 None 2 FRONT DIP SW Node Address ADD...

Страница 3: ...ECTOR DA DB DG SLD FG To Other Modbus Devices Note The FG terminal is not connected with the FG of the power supply module model R5 PS WIRING INSTRUCTIONS EURO TYPE CONNECTOR TERMINAL Modbus Applicabl...

Страница 4: ...within the slave 17 Report Slave ID Slave type RUN status 18 Program 884 M84 19 Reset Comm Link 20 Read General Reference 21 Write General Reference 22 Mask Write 4X Register 23 Read Write 4X Register...

Страница 5: ...T 4 Module 4 Ai 1 INT 16 Module 16 Ai 1 INT 17 18 Module 1 Ai 1 Float 19 20 Module 2 Ai 1 Float 21 22 Module 3 Ai 1 Float 23 24 Module 4 Ai 1 Float 47 48 Module 16 Ai 1 Float Holding Registers 4X 1 Mo...

Страница 6: ...hen there is an error in one or more channels the bit corresponding to the channels turns to 1 The bit corresponding to unmounted channels turns to 1 DC current output modules check output wire breakd...

Страница 7: ...eger section of raw data is directly converted into the data For example 135 4 F is con verted into 135 Negative values are represented in 2 s complements 0 15 4 POINT DISCRETE DATA models R5 DA4 DC4...

Отзывы: