manualshive.com logo in svg
background image

R3Y-DA16B

P. 1 / 2

EM-8969

 

Rev.1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201

 

Fax: +81(6)6659-8510

 

E-mail: [email protected]

AC CONTACT INPUT MODULE

(Di 16 points)

MODEL

R3Y-DA16B

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  AC contact input module ................................................... (1)

 MODEL NO.

Confirm that the model number described on the product to 
be exactly what you ordered.

 INSTRUCTION MANUAL

This manual describes necessary points of caution when you 
use this product, including installation, connection and basic 
maintenance procedures.

POINTS OF CAUTION

 

HOT SWAPPABLE MODULES

• Replacing the module does not affect other modules on 

the same base.  Thus, the module can be replaced while 
the power is ON.  However, replacing multiple modules 
at once may greatly change live voltage levels.  We highly 
recommend to replace them one by one.

 

GENERAL PRECAUTIONS

• DO NOT set the switches on the module while the power 

is supplied.  The switches are used only for maintenance 
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C  

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

INSTALLATION

Use the Installation Base (model: R3-BSx).

COMPONENT IDENTIFICATION

 STATUS INDICATOR LED

RUN indicator

: Bi-color (red/green) LED; 

Red when the bus A operates normally;

Green when the bus B operates normally;

Amber when both buses operate normally.

ERR indicator

: Bi-color (red/green) LED; 

Red with the excitation abnormality;

Green in normal operating conditions.

Input status indicator

: Red LED; turns on with the inputs sup-

plied.

 SIDE DIP SW

• Excitation Monitor

: SW3

SW

EXCITATION MONITOR

WITH (

*

)

WITHOUT

SW3-1

OFF

ON

(*) Factory setting
• 

Read Rate: 

SW3

SW

READ RATE (≤msec)

10 (

*

)

1

5

20

50

70

100

200

SW3-2

OFF

ON

OFF

ON

OFF

ON

OFF

ON

SW3-3

OFF

OFF

ON

ON

OFF

OFF

ON

ON

SW3-4

OFF

OFF

OFF

OFF

ON

ON

ON

ON

(*) Factory setting

•  Excitation Monitor Active

The input is held at the last status when the loss of excitation 
is detected. The excitation must be connected across CHK 
(4A/4B or 3A/3B) and COM (2A/2B or 1A/1B).

•  Excitation Monitor Inactive

All input signals are turned off when the loss of excitation is detected.

9

10

11

12

13

14

15

16

1

2

3

4

5

6

7

8

B

20

A

20

B

1

A

1

RUN LED

ERR LED

Status Indicator LED

Input Connector

■ 

FRONT VIEW

• Pin Assignment

■ 

SIDE VIEW

SW3

ON

4

3

2

1

Exc.

Monitor

Read

Rate

9

10

11

12

13

14

15

16

1

2

3

4

5

6

7

8

B

20

A

20

B

1

A

1

RUN LED

ERR LED

Status Indicator LED

Input Connector

■ 

FRONT VIEW

• Pin Assignment

■ 

SIDE VIEW

SW3

ON

4

3

2

1

Exc.

Monitor

Read

Rate