R3Y-DA16B
P. 1 / 2
EM-8969
Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201
Fax: +81(6)6659-8510
E-mail: [email protected]
AC CONTACT INPUT MODULE
(Di 16 points)
MODEL
R3Y-DA16B
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■
PACKAGE INCLUDES:
AC contact input module ................................................... (1)
■
MODEL NO.
Confirm that the model number described on the product to
be exactly what you ordered.
■
INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, including installation, connection and basic
maintenance procedures.
POINTS OF CAUTION
■
HOT SWAPPABLE MODULES
• Replacing the module does not affect other modules on
the same base. Thus, the module can be replaced while
the power is ON. However, replacing multiple modules
at once may greatly change live voltage levels. We highly
recommend to replace them one by one.
■
GENERAL PRECAUTIONS
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■
ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■
WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
INSTALLATION
Use the Installation Base (model: R3-BSx).
COMPONENT IDENTIFICATION
■
STATUS INDICATOR LED
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with the excitation abnormality;
Green in normal operating conditions.
Input status indicator
: Red LED; turns on with the inputs sup-
plied.
■
SIDE DIP SW
• Excitation Monitor
: SW3
SW
EXCITATION MONITOR
WITH (
*
)
WITHOUT
SW3-1
OFF
ON
(*) Factory setting
•
Read Rate:
SW3
SW
READ RATE (≤msec)
10 (
*
)
1
5
20
50
70
100
200
SW3-2
OFF
ON
OFF
ON
OFF
ON
OFF
ON
SW3-3
OFF
OFF
ON
ON
OFF
OFF
ON
ON
SW3-4
OFF
OFF
OFF
OFF
ON
ON
ON
ON
(*) Factory setting
• Excitation Monitor Active
The input is held at the last status when the loss of excitation
is detected. The excitation must be connected across CHK
(4A/4B or 3A/3B) and COM (2A/2B or 1A/1B).
• Excitation Monitor Inactive
All input signals are turned off when the loss of excitation is detected.
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
B
20
A
20
B
1
A
1
RUN LED
ERR LED
Status Indicator LED
Input Connector
■
FRONT VIEW
• Pin Assignment
■
SIDE VIEW
SW3
ON
4
3
2
1
Exc.
Monitor
Read
Rate
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
B
20
A
20
B
1
A
1
RUN LED
ERR LED
Status Indicator LED
Input Connector
■
FRONT VIEW
• Pin Assignment
■
SIDE VIEW
SW3
ON
4
3
2
1
Exc.
Monitor
Read
Rate