EM-8940  Rev.1  P. 3 / 4

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

1

20

130 (5.12)

27.5 (1.08)

109 (4.29)

120 (4.72)

POSITIONING

GUIDE

 

CONNECTION DIAGRAM

INTERNAL BUS A

*

1

INTERNAL BUS B

 

*

1. For dual redundant communication.

*

2. To use shield line, connect it to SLD terminal and ground the terminal 20.

Note: Do not connect wide span and narrow span simultaneously within the same 
          channel.  Do not use void terminals.

1

INTERNAL POWER

+

+

WIDE SPAN

NARROW SPAN

OUTPUT  1

3

2

5

+

+

WIDE SPAN

NARROW SPAN

OUTPUT  2

7

6

11

+

+

WIDE SPAN

NARROW SPAN

OUTPUT  3

13

12

15

+

+

WIDE SPAN

NARROW SPAN

OUTPUT  4

17

16

SLD

SLD

SLD

SLD

SLD
SLD

*

2

4

8

18

19

20

14

BUS CONNECTOR

 

Wide Span

:  -10 – +10 V DC, -5 – +5 V DC, 0 – 10 V DC, 

 0 – 5 V DC, 1 – 5 V DC

 

Narrow Span

: -1 – +1 V, 0 – 1 V DC

Содержание R3S-YV4

Страница 1: ...e highly recommend to replace them one by one GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for maintenance without the power ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous...

Страница 2: ...put Range SW1 SW2 OUTPUT 1 SW1 OUTPUT 2 SW1 RANGE OUTPUT 3 SW2 OUTPUT 4 SW2 1 2 3 4 5 6 7 8 OFF OFF OFF OFF OFF OFF OFF OFF 10 10V DC ON OFF OFF OFF ON OFF OFF OFF 5 5V DC OFF ON OFF OFF OFF ON OFF OFF 1 1V DC ON ON OFF OFF ON ON OFF OFF 0 10V DC OFF OFF ON OFF OFF OFF ON OFF 0 5V DC ON OFF ON OFF ON OFF ON OFF 1 5V DC OFF ON ON OFF OFF ON ON OFF 0 1V DC Output Hold SW3 1 SW OUTPUT HOLD HOLD OFF S...

Страница 3: ...NTERNAL BUS B 1 For dual redundant communication 2 To use shield line connect it to SLD terminal and ground the terminal 20 Note Do not connect wide span and narrow span simultaneously within the same channel Do not use void terminals 1 INTERNAL POWER WIDE SPAN NARROW SPAN OUTPUT 1 3 2 5 WIDE SPAN NARROW SPAN OUTPUT 2 7 6 11 WIDE SPAN NARROW SPAN OUTPUT 3 13 12 15 WIDE SPAN NARROW SPAN OUTPUT 4 17...

Страница 4: ...Be sure wire insulation is not inside the terminal Screw Driver Power wire OUTPUT PIN ASSIGNMENT PIN No FUNCTION 1 VH1 2 COM1 3 VL1 4 SLD 5 VH2 6 COM2 7 VL2 8 SLD 9 NC 10 NC 11 VH3 12 COM3 13 VL3 14 SLD 15 VH4 16 COM4 17 VL4 18 SLD 19 SLD 20 SLD FUNCTIONS OUTPUT HOLD or OUTPUT OFF In normal conditions the module outputs the signal from the preferred bus A When an error is detected the output is sw...

Отзывы: