R3S-RR8
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8934 Rev.1 P. 7 / 7
WIRING INSTRUCTIONS
■
APPLICABLE WIRE SIZE
•
Solid
: 0.2 to 1.0 mm
2
(0.55 to 1.12 dia.)
•
Stranded
: 0.2 to 1.5 mm
2
(Tinning wire ends may cause contact failure and therefore
is not recommended.)
• Ferruled:
Unsheathed: 0.25 to 1.5 mm
2
Sheathed: 0.25 to 0.75 mm
2
• Expose wire conductors by 10 mm (0.39”).
Stripped length
10mm
■
CONNECTION PROCEDURE
Insert the wire end until it comes to a full stop while push-
ing slot with the tip of a screw driver as shown below. Be
sure wire insulation is not inside the terminal.
Screw Driver
Power wire
OUTPUT PIN ASSIGNMENT
PIN No.
FUNCTION
1
Do 1
2
COM
3
Do 2
4
COM
5
Do 3
6
COM
7
Do 4
8
COM
9
Do 5
10
COM
11
Do 6
12
COM
13
Do 7
14
COM
15
Do 8
16
COM
17
COM
18
COM
19
COM
20
COM