R3S-RR8

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8934  Rev.1  P. 3 / 7

INPUT OUTPUT DATA BIT & DATA ALLOCATION

 

OUTPUT DATA BIT: 16 BITS (SW3-4: OFF)

When output data bit is 16 bits, set each output with 2 bits.
The table below shows data allocation.

BIT

SETTING

OPERATION

0, 1

0, 0

No operation

1, 0

Output 1 ON

0, 1

Output 1 OFF

1, 1

Output 1 RESET

2, 3

0, 0

No operation

1, 0

Output 2 ON

0, 1

Output 2 OFF

1, 1

Output 2 RESET

4, 5

0, 0

No operation

1, 0

Output 3 ON

0, 1

Output 3 OFF

1, 1

Output 3 RESET

6, 7

0, 0

No operation

1, 0

Output 4 ON

0, 1

Output 4 OFF

1, 1

Output 4 RESET

8, 9

0, 0

No operation

1, 0

Output 5 ON

0, 1

Output 5 OFF

1, 1

Output 5 RESET

10, 11

0, 0

No operation

1, 0

Output 6 ON

0, 1

Output 6 OFF

1, 1

Output 6 RESET

12, 13

0, 0

No operation

1, 0

Output 7 ON

0, 1

Output 7 OFF

1, 1

Output 7 RESET

14, 15

0, 0

No operation

1, 0

Output 8 ON

0, 1

Output 8 OFF

1, 1

Output 8 RESET

By setting with 2 bits, the module operates as shown above.  
ON or OFF can be set consecutively.  To output ON twice 
successively, set ON (1, 0), RESET (1, 1), and then set ON 
(1, 0) again.

 

OUTPUT DATA BIT: 8 BITS (SW3-4: ON)

When output data bit is 8 bits, set each output with 1 bit.
The table below shows data allocation.

BIT

SETTING

OPERATION

0

0

Output 1 OFF

1

Output 1 ON

1

0

Output 2 OFF

1

Output 2 ON

2

0

Output 3 OFF

1

Output 3 ON

3

0

Output 4 OFF

1

Output 4 ON

4

0

Output 5 OFF

1

Output 5 ON

5

0

Output 6 OFF

1

Output 6 ON

6

0

Output 7 OFF

1

Output 7 ON

7

0

Output 8 OFF

1

Output 8 ON

8

----

Unused

9

----

Unused

10

----

Unused

11

----

Unused

12

----

Unused

13

----

Unused

14

----

Unused

15

-----

Unused

ON or OFF cannot be set consecutively, because when each 
bit is “1”, ON is set and when each bit is “0”, OFF is set.

Содержание R3S-RR8

Страница 1: ...We highly recommend to replace them one by one GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for maintenance without the power ENVIR...

Страница 2: ...LED Red when the bus A operates normally Green when the bus B operates normally Amber when both buses operate normally ERR indicator Green LED OFF in abnormality ON in normal operating conditions Inpu...

Страница 3: ...N 0 1 Output 6 OFF 1 1 Output 6 RESET 12 13 0 0 No operation 1 0 Output 7 ON 0 1 Output 7 OFF 1 1 Output 7 RESET 14 15 0 0 No operation 1 0 Output 8 ON 0 1 Output 8 OFF 1 1 Output 8 RESET By setting w...

Страница 4: ...ut 6 ON 11 Reserved 12 0 Feedback input for output 7 OFF 1 Feedback input for output 7 ON 13 Reserved 14 0 Feedback input for output 8 OFF 1 Feedback input for output 8 ON 15 Reserved INPUT DATA BIT 8...

Страница 5: ...bit Word access Input 1 Output 1 Input 2 Output 2 Input 8 Output 8 Input 1 Output 1 Input 2 Output 2 Input 8 Output 8 0 0 I O data length is 16 bit Bit access 2 bits corresponds one I O Each bit in t...

Страница 6: ...B INTERNAL POWER 9 5 11 7 6 8 10 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8 COM COM 3 OUTPUT 2 OUTPUT 1 20 2 4 15 1 14 16 18 12 17 19 13 COM COM COM COM COM COM COM COM COM COM BUS CONNECT...

Страница 7: ...ecommended Ferruled Unsheathed 0 25 to 1 5 mm2 Sheathed 0 25 to 0 75 mm2 Expose wire conductors by 10 mm 0 39 Stripped length 10mm CONNECTION PROCEDURE Insert the wire end until it comes to a full sto...

Отзывы: