EM-9005 Rev.2 P. 5 / 5
WIRING INSTRUCTIONS
■
TIGHTENING TORQUE
Separable screw terminal wiring screw: 0.5 N·m
Separable screw terminal fixing screw: 0.5 N·m
■
SOLDERLESS TERMINAL unit: mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Applicable wire size: 0.25 to 0.75 mm
2
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.
3.2 (.13) dia.
12 (.47) max.
6 max
.
(.24)
3 (.12) max.
■
HOW TO REMOVE SEPARABLE SCREW TERMINAL
The terminal block is separable in two pieces. Evenly loos-
en two screws on top and bottom of the terminal block to
separate.
FUNCTIONS
■
OUTPUT AT THE LOSS OF COMMUNICATION
• Output Hold
If the network module is in error, the module holds the
signal at error and stands by until the communication re-
covers.
• Output set value
If the network module is in error, the module holds the
signal at error or power up and stands by until the com-
munication recovers. The signal at error or power up is se-
lectable with PC configurator software (Model: R30CFG).
Not depending on output at the loss of communication set-
ting, when power up the module holds the signal at error or
power up and stands by until the normal data is received.
PC CONFIGURATOR
The following parameter items can be set with using PC
Configurator Software (model: R30CFG).
Refer to the users manual for the R30CFG for detailed op-
eration of the software program.
■
CHANNEL INDIVIDUAL SETTING
PARAMETER
SETTING RANGE
DEFAULT
SETTING
Unused setting
CH enabled
CH disabled
CH enabled
Output range
-10 – +10 V DC
-5 – +5 V DC
0 – 10 V DC
0 – 5 V DC
1 – 5 V DC
-10 – +10 V DC
Fine zero adjustment -320.00 – +320.00 (%) 0.00 (%)
Fine gain adjustment -3.2000 – +3.2000
1.0000
Scaled range zero
-32 000 – +32 000
0
Scaled range span
-32 000 – +32 000
10 000
Output range at
communication
failure or power up
-15.00 – +115.00 (%) -15.00 (%)
■
CHANNEL BATCH SETTING
PARAMETER
SETTING RANGE
DEFAULT
SETTING
Simulate output
Normal output
Simulation data
Normal output
Output at the loss
of communication
Hold the output data
User set data output
Hold the out-
put data