R3-SS4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8393 Rev.5 P. 2 / 3
COMPONENT IDENTIFICATION
1
11
12
13
14
15
16
17
18
19
20
2
3
4
5
6
7
8
9
10
ON
8
7
6
5
4
3
2
1
SW1
SW2
ON
8
7
6
5
4
3
2
1
SW3
ON
4
3
2
1
■
FRONT VIEW
■
SIDE VIEW
ERR LED
RUN LED
Conv.
Rate
Input 2 (SW1)
or
Input 4 (SW2)
Range
Input 1 (SW1)
or
Input 3 (SW2)
Functions
■
STATUS INDICATOR LED
RUN indicator:
Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator:
Bi-color (red/green) LED;
Red with input circuit abnormality (AD con-
verter response failure);
Green in normal operating conditions.
■
SIDE DIP SW
(*) Factory setting
• Input Range: SW1, SW2
INPUT 1 (SW1)
INPUT 2 (SW1)
RANGE
INPUT 3 (SW2)
INPUT 4 (SW2)
1
2
3
4
5
6
7
8
OFF OFF OFF OFF OFF OFF OFF OFF 4 – 20mA (*)
ON OFF OFF OFF ON OFF OFF OFF 0 – 20mA
OFF ON OFF OFF OFF ON OFF OFF -20 – +20mA
• Conversion Rate: SW3-1, 3-2
SW
CONVERSION RATE
80 ms (
*
)
40 ms
20 ms
10 ms
SW3-1
OFF
ON
OFF
ON
SW3-2
OFF
OFF
ON
ON
Note: Be sure to set unused SW3-3 and 3-4 to OFF.
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.
■
CHANNEL INDIVIDUAL SETTING
PARAMETER
AVAILABLE RANGE
DEFAULT SETTING
Zero Scale
-32000 to +32000
0
Full Scale
-32000 to +32000
10000
Zero Adjust
-320.00 to +320.00
0.00
Full Adjust
-32000 to +32000
1.0000
Unused
0: Enable
1: Disable
0: Enable