background image

R3-NP1

P.  / 4

EM-848 Rev.3 

COMPONENT IDENTIFICATION

SW3

SA1
SA2

ON

4

3

2

1

1
2
3

4
5
6

5

4 3 2 1

0

9

8

7

6

5

4 3 2 1

0

9

8

7

6

RUN LED

■ 

FRONT VIEW

■ 

SIDE VIEW

ERR LED

Configuration Jack

Node Address Setting

Rotary SW, upper digit
Node Address Setting

Rotary SW, lower digit

Network Connector

 PROFIBUS INTERFACE

PIN NO.

SIGNAL

SIGNIFICANCE

1
2
3

NC
NC

B_line

Not used
Not used
Network, B-line

4
5
6

RTS

GND

P5V

RTS signal
0V
5V

7
8
9

NC

A_line

NC

Not used
Network, A-line
Not used

 FRONT ROTARY SW

• Node Address

: SA1, SA2

Node Address is set in Hexadecimal.

 SIDE DIP SW

• Dual Communication

: SW3

When  two  network  modules  are  mounted,  one  must  be 
‘Main’ (OFF) network and the other must be ‘Sub’ (ON) net-
work.  For single communication, the network module must 
always be set to ‘Main’ (OFF). 

SW

DUAL COMMUNICATION

MAIN (

*

)

SUB

SW3-1

OFF

ON

• Input Error Data

: SW3

Hold: 

When the communication from an input module is lost 

due to the input module error, the network module holds the 
signal and stands by until the communication recovers.

Set to ‘0’:

 When the communication from an input module 

is lost due to the input module error, the network module 
outputs ‘0.’

SW

INPUT ERROR DATA

HOLD (

*

)

SET ‘0’

SW3-2

OFF

ON

• LED Function

: SW3

Functions assigned to the front RUN and ERR LEDs can 

be selected.

When SW3-4 is OFF: R3 Network Status (*)

RUN

ERR

EXPLANATION

Green ON

OFF

Normal (Data_Exchange)

Green ON

Green Flash External Diagnostics

OFF

Green ON

Error (No Data_Exchange)

When SW3-4 is ON: PROFIBUS Status

RUN

ERR

EXPLANATION

EXTERNAL 

DIAGNOS-

TICS

OFF

OFF

No Power

---

ON (Orange)

OFF

No Connection

No

Flash (Red)

Yes

Flash

(Green/Orange)

OFF

Para / Cfg

No

Flash (Red)

Yes

ON (Green)

OFF

Data_Exchange

No

Flash (Red)

Yes

(*) Factory setting

6

9

1

5

Отзывы: