PC CONFIGURATOR

The following parameter items can be set with using PC Configurator Software (model: R3CON).
Refer to the users manual for the R3CON for detailed operation of the software program.

 

NETWORK MODULE SETTING 

PARAMETER

SETTING RANGE

DEFAULT SETTING

Time (no communication time)

0.2 – 3200.0 (sec.)

3.0 (sec.) 

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch) 

1

2

3

4

5

6

130 (5.12)

27.5 (1.08)

109 (4.29)

POSITIONING

GUIDE

TERMINAL

COVER

6–M3

SCREW

6.2

(.24)

 

CONNECTION DIAGRAM

Note:  In order to improve EMC performance, bond the FG 

terminal to ground.

Caution: FG terminal is NOT a protective conductor terminal.

INTERNAL POWER

INTERNAL BUS

DG

DB
DA

SLD

FG

To Other

CC-Link

Devices

CONFIGURATION JACK

JACK

BUS CONNECTOR

*

Not provided with ‘No Power Supply’ type module.

1

4

RUN 

+

RUN 

RUN CONTACT OUTPUT

2

3

6

U (+) 

V (–) 

FG

POWER INPUT

*

*

WIRING INSTRUCTIONS

 

M3 SCREW TERMINAL (power input, RUN contact output) 

Torque: 0.5 N·m

 

SOLDERLESS TERMINAL 

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.
Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.75 to 1.25 mm

2

12max

6max

3max

4min

3.2 dia.

(mm)

 

EURO TYPE CONNECTOR TERMINAL (CC-Link)

Applicable wire size: 0.2 to 2.5 mm

2

 (AWG24 to 12)

Stripped length: 7 mm

Содержание R3-NC1

Страница 1: ...Hz approx 20VA 24V DC rating 24V 10 approx 12W GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for maintenance without the power ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuou...

Страница 2: ...ough 8 Setting for No 9 and later modules is identical to No 8 SW ASSIGNMENT MODULE NO SW1 1 SW1 2 1 SW1 3 SW1 4 2 SW1 5 SW1 6 3 SW1 7 SW1 8 4 SW2 1 SW2 2 5 SW2 3 SW2 4 6 SW2 5 SW2 6 7 SW2 7 SW2 8 8 SW SETTING DATA ALLOCATION OFF OFF 1 ON OFF 4 OFF ON 8 ON ON 16 Refer to the specifications of the related series for the Data Allocation Type of I O modules Dual Communication SW3 1 When two network m...

Страница 3: ...M Note In order to improve EMC performance bond the FG terminal to ground Caution FG terminal is NOT a protective conductor terminal INTERNAL POWER INTERNAL BUS DG DB DA SLD FG To Other CC Link Devices CONFIGURATION JACK JACK BUS CONNECTOR Not provided with No Power Supply type module 1 4 RUN RUN RUN CONTACT OUTPUT 2 3 6 U V FG POWER INPUT WIRING INSTRUCTIONS M3 SCREWTERMINAL power input RUN conta...

Страница 4: ...the data sent from the master to the network module OUTPUT DATA The figure below shows the allocation of the data sent from the network module to the master INPUT DATA The figure below shows the allocation of the data sent from the master to the network module Sixteen 16 data areas are available Total data areas occupied by I O modules must be within this limitation The DIP SW located at the side ...

Страница 5: ... mod ule turns to 1 R3 TSx R3 RSx R3 US4 Input burnout R3 DA16A Power input in error or disconnected R3 YSx Output current error e g load unconnected R3 PC16A External power supply in error or disconnected Data Error Status RX n 2 0 through RX n 2 F indicate overrange R3 US4 out of 10 to 110 the other types out of 15 to 115 status for each module The bit corresponding to such module turns to 1 RX ...

Страница 6: ...nge represented in 2 s complement 0 15 TEMPERATURE DATA 16 bit data models R3 RS4 TS4 and US4 etc 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converted into the data For example 135 4 F is con verted into 135 Minus temperature is converted into negative values re...

Страница 7: ...PLC RY n 1 0 0 R3 main network RY n 1 0 1 RY n 1 0 0 R3 sub network 1 2 3 4 5 1 When the PLC master control standby system bit is undefined due to no communication the both host PLCs function as standby system for each of R3 main and sub network modules All contact outputs are off and analog output modules output 15 2 The master PLC communicates with the R3 main network module while the standby PL...

Страница 8: ...the Master Unit X0020 Only when required Number of connected modules Number of retries Number of automatic return modules Operation specification when the CPU is down Reserved station specification X002F M0 M1 PLS M0 SET M1 RST M1 MOV D0 MOV D1 MOV D2 T0 H0002 H0001 D0 K3 T0 H0002 H0006 D3 K1 MOV D3 M1 MOV D13 MOV D T0 H0002 H0020 D13 K M1 MOV D4 MOV D5 MOV D6 MOV D7 MOV D8 MOV D9 MOV D10 MOV D11 ...

Отзывы: