R3-CT8A

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8444  Rev.3  P. 2 / 4

COMPONENT IDENTIFICATION

SW2

SW1

ON

1

2

3

4

5

6

7

8

ON

ON

1

2

3

4

5

6

7

8

SW3

1

2

3

4

5

19
20
21
22

15
16
17
18

23
24
25
26
27
28

6
7
8
9

10
11
12
13
14

1
2
3
4

■ 

FRONT VIEW

ERR LED

RUN LED

■ 

SIDE VIEW

Range
Input 1-4 (SW1)

  or

Input 5-8 (SW2)

Conv.

Rate

Functions

 

SIDE DIP SW

(*) Factory setting

• Input Range: SW1, SW2 

(selectable per 4 channels)

INPUT 1 through INPUT 4 (SW1)

RANGE

INPUT 5 through INPUT 8 (SW2)

1

2

3

4

OFF

OFF

OFF

OFF

CLSA-50 (*)

ON

OFF

OFF

OFF

CLSA-30

OFF

ON

OFF

OFF

CLSA-12

ON

ON

OFF

OFF

CLSA-08

• Conversion Rate: SW3-1, 3-2

SW

CONVERSION RATE

160 ms (

*

)

80 ms

40 ms

20 ms

SW3-1

OFF

ON

OFF

ON

SW3-2

OFF

OFF

ON

ON

Note:  Be sure to set unused SW1-5 through 1-8, SW2-5 

through 2-8, SW3-3 and 3-4 to OFF.

 

STATUS INDICATOR LED

RUN indicator:

 Bi-color (red/green) LED; 

Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

ERR indicator:

 Bi-color (red/green) LED; 

Red with input abnormality;
Green in normal operating conditions.

PC CONFIGURATOR

With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Zero Scale

-32000 to +32000

0

Full Scale

-32000 to +32000

10000

Zero Adjust

-320.00 to +320.00

0.00

Full Adjust

-32000 to +32000

1.0000

Zero Base

Depends on sensor type

0.00

Full Base

Depends on sensor type

0.00

Unused

0: Enable
1: Disable

0: Enable

Содержание R3-CT8A

Страница 1: ...is ON However replacing multiple modules at once may greatly change live voltage levels We highly recommend to replace them one by one GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for maintenance without the power ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housin...

Страница 2: ...ION RATE 160 ms 80 ms 40 ms 20 ms SW3 1 OFF ON OFF ON SW3 2 OFF OFF ON ON Note Be sure to set unused SW1 5 through 1 8 SW2 5 through 2 8 SW3 3 and 3 4 to OFF STATUS INDICATOR LED RUN indicator Bi color red green LED Red when the bus A operates normally Green when the bus B operates normally Amber when both buses operate normally ERR indicator Bi color red green LED Red with input abnormality Green...

Страница 3: ...510 E mail info m system co jp EM 8444 Rev 3 P 3 4 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch TERMINAL COVER 5 19 20 21 22 15 16 17 18 23 24 25 26 27 28 6 7 8 9 10 11 12 13 14 1 2 3 4 130 5 12 27 5 1 08 109 4 29 POSITIONING GUIDE 28 M3 SCREW 6 2 24 ...

Страница 4: ... 18 19 LOAD SOURCE k l LOAD SOURCE k l INPUT 7 21 22 INPUT 8 24 25 LOAD SOURCE k LOAD SOURCE l CONNECTOR CLAMP ON SENSOR CONNECTOR CLAMP ON SENSOR CONNECTOR CLAMP ON SENSOR CONNECTOR CLAMP ON SENSOR Connector provided only for the CLSA 08 and CLSA 12 For dual redundant communication k l l k WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recomme...

Отзывы: