background image

R3-AS4

P. 1 / 3

EM-8439 Rev.1

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check
the contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.

■ 

PACKAGE INCLUDES:

DC current input alam module .................................. (1)

■ 

MODEL NO.

Check that model No. described on the specification label is
exactly what you ordered.

■ 

INSTRUCTION MANUAL

This manual describes necessary points of caution when you
use this product, including installation, connection and basic
maintenance procedures.

INSTRUCTION  MANUAL

MODEL

R3-AS4

DC CURRENT INPUT ALARM MODULE

(4 points, isolated)

POINTS OF CAUTION

■ 

CONFORMITY WITH EC DIRECTIVES

• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated in
a panel system.  The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.

■ 

HOT INSERTION/REMOVAL OF MODULES

Removing or replacing modules does not affect other modules
on the same backplane.  It is possible to replace them without
removing the power supply.  However, replacing multiple
modules at once may greatly change line voltage levels.  We
recommend that you replace them one by one.

■ 

ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventila-
tion.
• Do not install the unit where it is subjected to continuous
vibration.  Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55

°

C

(14 to 131

°

F) with relative humidity within 30 to 90% RH in

order to ensure adequate life span and operation.

■ 

WIRING

• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present.  Do not install them in the same duct.

■ 

UNUSED INPUT CHANNELS

• Set the unused input channels to 

±

20mA or 0 – 20mA range.

Unused channels left open with 4 – 20mA setting are equal
to the input lower than -15%, which sets a data abnormality
at the PLC or the host device.
Open circuit with the input range set to 

±

20mA means 50%

of the full-scale.  An alarm setpoint must be set to a value
that does not trip an unwanted alarm.
• Unused channels can be specified and set so on the PC
Configurator Software (model: R3CON) without needing the
above mentioned setting.

■ 

AND ....

• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.

INSTALLATION

Use the Installation Base (model: R3-BSx).