background image

R3-AS4

P. 2 / 3

EM-8439 Rev.1

COMPONENT IDENTIFICATION

Conversion Rate

: SW3

SW

CONVERSION RATE

80 ms (

*

)

40 ms

20 ms

10 ms

SW3-1

OFF

ON

OFF

ON

SW3-2

OFF

OFF

ON

ON

(*) Factory setting

1

11

12

13

14

15

16

17

18

19

20

2

3

4

5

6

7

8

9

10

ON

8
7
6
5
4
3
2
1

SW1

SW2

ON

8
7
6
5
4
3
2
1

SW3

ON

4
3
2
1

FRONT VIEW

SIDE VIEW

ERR LED

RUN LED

Conv.
Rate

Input 2 (SW1)
  or
Input 4 (SW2)

Range

Input 1 (SW1)
  or
Input 3 (SW2)

SIDE DIP SW

Input Range

: SW1, SW2

INPUT 1 (SW1)

INPUT 2 (SW1)

INPUT 3 (SW2)

INPUT 4 (SW2)

RANGE

1

2

3

4

5

6

7

8

OFF OFF OFF OFF OFF OFF OFF OFF 4 – 20mA (*)

ON OFF OFF OFF ON OFF OFF OFF 0 – 20mA

OFF ON OFF OFF OFF ON OFF OFF -20 – +20mA

OUTPUT DATA DESCRIPTIONS

Four alarm setpoints are selectable per each input.  One (1)
word (16 bit) data is transmitterd to the PLC or the host
device via the R3 network module.

0

15

Alarm 1
Alarm 2

Input 1

Alarm 3
Alarm 4

Alarm 1
Alarm 2

Input 2

Alarm 3
Alarm 4

Alarm 1
Alarm 2

Input 3

Alarm 3
Alarm 4

Alarm 1
Alarm 2

Input 4

Alarm 3
Alarm 4

ALARM SETTING

The following parameters are programmable using the PC
Configurator Software (model: R3CON).

ALARM TRIP POINT (-15.00 to +115.00%)

Four alarm setpoints are selectable per each input.

ALARM TYPE (High or Low)

High or Low alarm is selectable for each alarm trip point.
High alarm: An alarm is set when the input signal goes above
the setpoint.
Low alarm: An alarm is set when the input signal goes be-
low the setpoint.

DEADBAND (HYSTERESIS)

   (0.00 to 100.00%; factory set to 5.00)

Deadband (deviation between the points where the alarm is
set and reset) is selectable for each alarm trip point.

POWER ON DELAY TIME

   (0.0 to 99.0 seconds; factory set to 5.0)

The alarm output start functioning in the preset time after
the power has been turned on.
This setting is common to all four points.

ALARM ON DELAY TIME

   (0.0 to 99.0 seconds; factory set to 1.0)

The alarm output is set when the preset time elapses after
the input has entered in the alarm range.
This setting is common to all four points.

ALARM HOLD TIME

   (0.0 to 99.0 seconds; factory set to 1.0)

The alarm output is held for the preset time even if it is
reset in shorter time.
This setting is common to all four points.

STATUS INDICATOR LED

RUN indicator

: Bi-color (red/green) LED;

Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

ERR indicator

: Bi-color (red/green) LED;

Red with the input abnormality;
Green in normal operating conditions.

Отзывы: