WIRING CONNECTION
Remove the transparent cover for terminal box and wire to the terminal block according to the below figure.
The unit can be operated once the power voltage and input signal are connected.
Also wire retract/UP, extend/DOWN, alarm, and/or output signals, as necessary.
Modbus communication allows operation without analog input and monitoring of the operation status of the unit.
+
–
+
–
INPUT
OUTPUT
a
b
UP/CCW SIG.
a
b
DOWN/CW SIG.
a
b
ALARM SIG.
FE
U(+)
V(–)
POWER
DA
DB
Modbus
DG
COMMUNICATION CABLE CONNECTIONS
Master Unit
DA
DB
DG
PSP10
PSP10
DA
DB
DG
I/O Unit
Terminating resistor
Terminating resistor
Terminating resistors can be turned ON/OFF on the PC configurator software (model: STCFG)
or programming unit (model: PU-2x).
Tx+/Rx+
Tx-/Rx-
SG