LINEARIZATION TABLE
Max. 32 calibration points defined by sets of input and output values can be programmed. Use only necessary number of
points, arranged in order from the smallest input value.
-15%
0
X01
X02
X03
X04
X05 +115%
Y01
Y02
Y03
Y04
+100% Y05
INPUT
OUTPUT
-5%
START
COMPLETE
Go to the PROGRAM mode
Go to the MONITOR mode
Create Linearization Table
• Set the 1st calibration point (input & output) to ITEM 21/22
• Set the 2nd calibration point (input & output) to ITEM 23/24
[e.g.] Set the 2nd input point to 50.0%, output point to 20.0%
• Press ITEM or key until the display shows ITEM 23
• Press DATA or key until the DATA display shows 50.0
• Press ITEM or key until the display shows ITEM 24
• Press DATA or key until the DATA display shows 20.0
Enable Linearization Table
• Press ITEM or key until the display
shows ITEM 20
• Press DATA or key until the display
shows DATA 1
Disable Linearization Table
• Press ITEM or key until the display
shows ITEM 20.
• Press DATA or key until the display
shows DATA 0.
Need Linearization?
YES
NO