SELECTING OUTPUT RANGE
[E.G.] Output range -10.0 to 10.0V modified to 1.0 to 5.0V
1. Turn the unit into Program Mode.
2. 0% Output
Choose ITEM 21 – DATA 1.0.
3. 100% Output
Choose ITEM 22 – DATA 5.0.
4. Turn the unit into Monitor Mode.
5. Set to ITEM P.
■
TARE ADJUSTMENT
1. Turn the unit into Program Mode.
2. Contact Input Function
Choose ITEM 18 – DATA 0.
3. Turn the unit into Monitor Mode.
(ITEM 18 is set to DATA 0 as default. No need of
conducting 1 through 3.)
4. Set to ITEM P.
5. Close across the contact input terminals (Di).
By the abovementioned procedure, the tare value is stored in
ITEM 10, the PV display shows the value set by 0% Scaling
Value, and the transmitter outputs the value set by 0%
Output.
The abovementioned procedure is applicable to modifications
from default setting.
80 (3.15)
50 (1.97)
103 (4.06)
132 (5.20)
20
(.79)
•When mounting, no extra space is needed between units.
5
6
7
8
2
1
11
10
[3.3 (.13)]
80 (3.15)
35.4 (1.39)
40 (1.57)
50 (1.97)
7.8 (.31)
CLAMP
(top & bottom)
DIN RAIL
35mm wide
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
11–M3.5
SCREW
3
9
4
■
DIMENSIONS mm (inch)
■
CONNECTION DIAGRAM
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram label on top of the unit.
U(+)
V(–)
POWER
7
8
+
–
OUTPUT
1
2
10
3
9
11
6
STRAIN
GAUGE
+
–
+
–
+
–
CONTACT
INPUT (Di)
INPUT
EXC.
4
5