MXLC

P. 2 / 5

EM-1704 Rev.7

FRONT PANEL CONFIGURATION & PROGRAMMING

 PROGRAMMING PROCEDURE

1) Press ITEM UP or DOWN key until ITEM display indicates “01”.
2) Press DATA UP or DOWN key and choose “2” on DATA display.

1  : Data indication only.
2  : All parameters are modifiable.

3) Press ITEM UP or DOWN key until ITEM display shows the ITEM

No. you need to change.

4) Press DATA UP or DOWN key and choose a DATA No. or value you

need on DATA display.

5) Repeat above 3 and 4.  (Entered data is stored 1 sec. after the

operation has been complete.)

6) Press ITEM UP or DOWN key until ITEM display indicates “01”.
7) Press DATA UP or DOWN key and choose “1” on the display.
8) Press ITEM UP or DOWN key until ITEM display indicates “P”.  DATA display shows process input.  You can now check data

setting by choosing ITEM No.

Note : DO NOT press UP and DOWN keys simultaneously.

PL4

PL3

PL2

PL1

DATA

ITEM

DATA

ITEM

ITEM No. Display

DATA UP-DOWN Keys

ITEM No. UP-DOWN Keys

DATA Display

Contact
Input LED

Polarity LED

ITEM

DATA

CONTENTS

DEFAULT

P

N/A

-9999 – 9999

Input display in engineering unit (as set in ITEM 14/15)

––

01

1, 2

Modification code

1 : Data indication only.

1

2 : All parameters are modifiable.

02

N/A

0 – 99

Status indication (“0” is normally indicated.)

0

0 : Normal          1  : Memory error
10 : PV overrange (out of -9999 to 9999)
20 : Input overrange (out of -15 to +115%)

03

N/A

0, 1, 2

Input range code

0 : S1 (0.0 –   3.0mV/V)

User specified

1 : S2 (0.0 – 10.0mV/V)
2 : S3 (0.0 – 30.0mV/V)

04

N/A

0, 1, 2

Output range code

0 : V1 (-1 – +1V)

User specified

1 : V2 (-10 – +10V)
2 : Z1 (0 – 20mA)

05

2

0.1 – 12.0

Excitation voltage  (V)

1.0

06

2

0.010 – 3.000

Sensor sensitivity

S1 : 0.0 –   3.0mV/V

  3.000mV/V

0.010 – 9.999

S2 : 0.0 – 10.0mV/V

  9.999mV/V

0.10 – 30.0

S3 : 0.0 – 30.0mV/V

30.00mV/V

Used when adjusting the sensor sensitivity by its rating value.
Set ITEM 07 before 06.

07

2

-30.00 – 30.00

0% input voltage

S1 : -30.00 – 30.00mV

-99.99 – 99.99

S2 : -99.99 – 99.99mV

-300.0 – 300.0

S3 : -300.0 – 300.0mV

Sensor's zero adjustment.  Approximate offset voltage.

08

2

-30.00 – 30.00

100% input voltage

S1 : -30.00 – 30.00mV

-99.99 – 99.99

S2 : -99.99 – 99.99mV

-300.0 – 300.0

S3 : -300.0 – 300.0mV

Used when adjusting the sensor sensitivity with an actual load.
Set ITEM 07 before 08.

09

2

10.0 – 100.0

Load ratio (%)

100.0

Used when adjusting the sensor sensitivity with an actual load.

10

2

-999.9 – 999.9

Tare adjustment (%)

0.0

11/L

N/A

-15.0 – 115.0

Input indicated in % with ITEM 01 DATA 1 (of the range set in ITEM 06/07/08)

––

Loop test output with ITEM 01 DATA 2 (‘L’ is indicated as ITEM No.)
(Use DATA UP/DOWN key to set the output signal.)

12

2

-99.99 – 99.99

Zero adjustment (%) (fine adj. of the value set in ITEM 06/07/08)

0.00

13

2

0.000 – 9.999

Gain adjustment (fine adj. of the value set in ITEM 06/07/08)

1.000

14

2

-9999 – 9999

Display range scaling     0% *

1

0

15

2

-9999 – 9999

Display range scaling 100% *

1

100

16

2

0, 1, 2, 3

Decimal point position

0 : _ _ _ _

1

1 : _ _ _ . _
2 : _ _ . _ _
3 : _ . _ _ _

17

2

0, 1, 2, 3, 4

Moving average (sampling cycle: 200 msec.)

0

0: No     1: 4 samples     2: 8 samples     3: 16 samples     4: 32 samples

MDF.

CODE