TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on top of the unit.

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3)  Input:  Check voltage across the input terminals 5 (+) – 6 

(–) with a multimeter.

4)  Output at STOP signal OFF:  The output does not track 

the input signal.

5)  Output load:  Check that the load resistance meets the 

described specifications.

ADJUSTMENT PROCEDURE

Use a signal source and measuring instruments of sufficient 

accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.
1)  Reset all setting.

2)  Turn the unit into Program mode.
3)  Simulate 0% input and adjust the PV display to show 0.0 

(ITEM 04).

4)  Simulate 100% input and adjust the PV display to show 

100.0 (ITEM 05).

5)  Simulate 0% input again and check the PV display.
6)  When the PV value is changed, repeat the above proce

-

dure 3) – 5).

7)  Simulate 0% input and adjust the output to 0%  (ITEM 

06).

8)  Simulate  100%  input  and  adjust  the  output  to  100%  

(ITEM 07).

9)  Simulate 0% input again and check the output.

10

) When the output value is changed, repeat the above pro

-

cedure 7) – 8).

11) Return the unit into Monitor mode.

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%,  75%  and  100%  input  signal.    Check  that  the  output 

signal for the respective input signal remains within accu-

racy described in the data sheet.  When the output is out of 
tolerance,  recalibrate  the  unit  according  to  the “ADJUST

-

MENT PROCEDURE” explained earlier.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS

  unit: mm (inch)

80 (3.15)

50 (1.97)

103 (4.06)

132 (5.20)

20 (.79)

• When mounting, no extra space is needed between units.

5

6

7

8

2

1

11

10

[3.3 (.13)]

80 (3.15)

35.4 (1.39)

40 (1.57)

50 (1.97)

7.8 (.31)

CLAMP

(top & bottom

)

DIN RAIL

35mm wide

2–4.5 (.18) dia.

MTG HOLE

25 (.98) deep

11–M3.5

SCRE

W

3

9

4

1

7 U(+)

V(–)

8

POWER

+

OUTPUT

2

+

INPUT

5

6

From COMPUTER

3

4

10

11

UP

9

From SOFT-TERMINAL

DOWN

COM

STOP

Effective only
in MAN mode

Отзывы: