ITEM  

MDF.

 

DATA 

CONTENTS 

    

DEFAULT

  

CODE

 

  21 

0, 1 – 60 

Power-saving mode 

0  : Continuous display 

10

 

 

 

 

 

1 – 60 : Time before display turned off (minutes)

  24 

0, 1 

DOWN input logic 

0  : True at LOW or Shortcircuit 

0 *

2

 

 

 

 

 

1  : True at HIGH or Opencircuit

  25 

0, 1 

UP input logic 

0  : True at LOW or Shortcircuit 

0 *

2

 

 

 

 

 

1  : True at HIGH or Opencircuit

  26 

0 – 3 

STOP input logic 

0  : AUTO mode at LOW or Shortcircuit 

2 *

2

 

 

 

 

 

    (Input updating halted at STOP)

 

 

 

 

 

1  : AUTO mode at HIGH or Opencircuit

 

 

 

 

 

    (Input updating halted at STOP)

 

 

 

 

 

2  : AUTO mode at LOW or Shortcircuit

 

 

 

 

 

3  : AUTO mode at HIGH or Opencircuit

  27 

-1.00 – 1.00 

Input code S1 

    0% input voltage (V) *

3

 -1.00

  28 

-1.00 – 1.00 

 

100% input voltage (V) *

3

 1.00

  27 

-10.0 – 10.0 

Input code S2 

    0% input voltage (V) *

3

 -10.0

  28 

-10.0 – 10.0 

 

100% input voltage (V) *

3

 10.0

  27 

-30.0 – 30.0 

Input code S3 

    0% input voltage (V) *

3

 -30.0

  28 

-30.0 – 30.0 

 

100% input voltage (V) *

3

 30.0

  29 

-1.00 – 1.00 

Output code V1 

    0% output voltage (V) *

4

 -1.00

  30 

-1.00 – 1.00 

 

100% output voltage (V) *

4

 1.00

  29 

-10.0 – 10.0 

Output code V2 

    0% output voltage (V) *

4

 -10.0

  30 

-10.0 – 10.0 

 

100% output voltage (V) *

4

 10.0

  29 

0.0 – 20.0 

Output code Z1 

    0% output current (mA) *

4

 4.0

  30 

0.0 – 20.0 

 

100% output current (mA) *

4

 20.0

  31 

-15.0 – 114.9 

Lower output limit 

    

-15.0

  32 

-14.9 – 115.0 

Upper output limit 

    

115.0

  33 

0, 1 

Reset all settings *

5

 

    

0

  34 

N/A 

--- 

ROM version 

    

---

*1 : Of the range set in ITEM 04/05.  ITEM 08 < ITEM 09.

*2 : Use the default setting when combining with the ST/STL.

*3 : ITEM 27 < ITEM 28.          *4 : ITEM 29 < ITEM 30.

*5 : Press DATA UP key and choose DATA 1.  Double-click DATA DOWN key.  The display shows DATA 0 after the initialization is  

 complete.

 SELECTING INPUT RANGE

[E.G.] -5.0 to 5.0V DC
1)  Program Mode
  Set  ITEM  01  –  DATA  2  to  turn  the  unit  into  Program 

Mode.

2)  0% Input Voltage
  Choose ITEM 27 – DATA -5.0.
3)  100% Input Voltage
  Choose ITEM 28 – DATA 5.0.

4)  Monitor Mode

  Set  ITEM  01  –  DATA  1  to  turn  the  unit  into  Monitor 

Mode.

5)  PV Indication
  Press ITEM UP or DOWN key until ITEM display indi

-

cates “P”.

 SELECTING OUTPUT RANGE

[E.G.] -10.0 to 0.0V DC
1)  Turn the unit into Program Mode.
2)  0% Output Voltage
  Choose ITEM 29 – DATA -10.0.
3)  100% Output Voltage
  Choose ITEM 30 – DATA 0.0.

4)  Turn the unit into Monitor Mode.

5)  Set to ITEM P.

 DISPLAY RANGE SCALING

[E.G.] PV display range -10.0 to 10.0 modified to show -6500 

to 350

1)  Turn the unit into Program Mode.
2)  Decimal Point Position
  Choose ITEM 10 – DATA 0.

3)  0% Scaling Value
  Choose ITEM 08 – DATA -6500.
  (Negative  [–]  range  is  identified  with  the  PL1  turned 

on.)

4)  100% Scaling Value
  Choose ITEM 09 – DATA 350.
5)  Turn the unit into Monitor Mode.
6)  Set to ITEM P.

 RESET ALL SETTINGS

Returning the unit into the factory-default settings.
1) 

Turn the unit into Reset Mode.  Choose ITEM 01 - DATA 3.

2)  Call up the Reset menu.

  Choose ITEM 33 – DATA 1. (Press DATA UP key.)

3)  Resetting Enable

  Double-click DATA DOWN key.  DATA 0 is displayed af

-

ter the initialization is complete.

4)  Turn the unit into Monitor Mode.

If necessary, go to Moving Average and other adjustments.

Set the unit to Monitor Mode other than for programming.

OPERATION IN DEFAULT SETTING

• When the STOP signal from the computer is ON:  

The MXAB tracks the computer input.

• When the STOP signal from the computer is OFF:  

The MXAB holds the value just before the OFF signal.

The output signal can be increased or decreased manually 

by giving UP or DOWN signals ON.  If both UP and DOWN 

signals are ON, the output remains held.