INSTALLATION

Refer to the drawings below.

 

EXTERNAL DIMENSIONS mm (inch)

50 (1.97)

110 (4.33)

70 (2.76)

20 (.79)

65 (2.56)

77 (3.03)

85 (3.35)

8 (.31)

U

V

G

u

v

4–4 (.16) dia.

SURGE

SIDE

PROTECT

SIDE

ALM

 

MOUNTING REQUIREMENTS mm (inch)

50 (1.97)

77 (3.03)

90 (3.54) min.

77 (3.03)

4–M3

SCREW

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.
Be sure to cross-wire between the Ground terminal (G) and metallic housing of the protected equipment. (100Ω max.)

MMD-24

S2

S1

P2

P1

+

4 – 20mA

DC

MMA-100

MMA-200

BREAKER

Be sure to

install

the breaker.

V

U

v

u

AC

Source

V

U

G

G

G

EQUIP-

MENT

 

GROUNDING

M-RESTER

PROTECTED

EQUIPMENT

G

G

CROSSOVER WIRE

GROUNDING

(100 ohms or less)

A crossover wire between M-RESTER ground and ground or metallic 

housing of equipment is required for protection.

If the protected equipment has no ground terminal, ground the 

M-RESTER only.