background image

M2YV

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5020  Rev.4  P. 2 / 3

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
When an input resistor is provided with the module, attach it together with input wiring to the input screw terminals.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

5

9

21.5 (.85)

70.5 (2.78)

84 (3.31)

10 (.39)

15 (.59)

6 (.23)

59 (2.32)

DIN RAIL

35mm wide

[4 (.16)]

8–M3

SCREW

72 (2.83)

23 (.91)

2–4.2x5

(.17x.20)

MTG HOLE

6 (.24) deep

114 (4.49)

• When mounting, no extra space is needed between units.

4

8

12
14 13

1

4 (.16)

 

CONNECTION DIAGRAM

1

4

+

*

*

Input shunt resistor attached for current input.

INPUT

R

+

OUTPUT

9

12

U(+)

V(–)

POWER

13

14

 

TERMINAL ASSIGNMENTS  unit: mm (inch)

5

8

9

12
14 13

INPUT RESISTOR

(model: REM2)

19 (.75)

Input shunt resistor attached

for current input.

1

4

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.