M2XRP2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5059  Rev.8  P. 3 / 5

 

CONNECTION DIAGRAM

CONFIGURATOR

JACK

+

OUTPUT

7

8

U(+)

V(–)

POWER

10

11

+

OUTPUT

7

8

U(+)

V(–)

POWER

10

11

CONFIGURATOR

JACK

ROTARY

ENCODER

ROTARY

ENCODER

■ 

RS-422 LINE DRIVER PULSE INPUT

■ 

OPEN COLLECTOR, VOLTAGE PULSE INPUT

4

+ 1

5

2

+

+

A

B

COM

PWR

+

1

2

+

3

6

A

PWR

A

COM

+

4

5

B

B

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Check DIP switch setting.
3) Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

4) Input:  Check that the input voltage is within 0 – 100% of 

full-scale.

5) Output:  Check that the load resistance meets the de-

scribed specifications.

6) Status indicator LED:  Check that it blinks in the normal 

patterns.

ZERO/SPAN ADJUSTMENTS

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, fine zero and span adjustments can 
be done to ±5% by pressing UP/DOWN switches enabled 
with the zero/span selector switch.  Calibrated values are 
stored in the non-volatile memory, which will not be lost 
even when you turn off power supply to the unit.
Zero and span are respectively set to 0% and 100% at the 
factory.

UP/DOWN Switches

The front cover cannot be opened to 180 deg. 

when flush with neighboring units.

Configurator Jack

■ 

FRONT VIEW (with cover open)

■ 

LEFT SIDE VIEW (with cover removed)

Input Monitor LED, PL1

Input Monitor LED, PL2

Status Indicator LED

Zero/Span Selector

Top: SPAN

Middle: OFF

Bottom: ZERO

1

4
3
2
1

2

3

4

ON

ON

OFF

OFF ON OFF

ON OFF

SW3

SW1

SW2

SW4

Input Selector SW

Output Selector SW

1
2

1
2

Zero/Span Selector

 

ZERO

:   UP/DOWN switches usable for zero adjustment.

 

OFF

:   UP/DOWN switches unavailable.

 

SPAN

:   UP/DOWN switches usable for span adjustment.

UP/DOWN Switches

 

UP

:    

Pressing UP increases adjusted values.

 

DOWN

:  Pressing DOWN decreases adjusted values.

 

HOW TO CALIBRATE THE ZERO

Slide the Zero/Span Selector to the bottom position and 
press UP or DOWN switch.  Incrementing speed will be 
doubled when you keep pressing a switch.

 

HOW TO CALIBRATE THE SPAN

Slide the Zero/Span Selector to the top position and press 
UP or DOWN switch.  Incrementing speed will be doubled 
when you keep pressing a switch.

 

HOW TO RESET

After you calibrated manually with these switches, you 
can reset them to its ex-factory state by pressing both UP/
DOWN switches at once.

 

ADJUSTMENT PROCEDURE

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 20 minutes.

1) ZERO:  Apply 0% input.  Slide the Zero/Span Selector to 

the bottom position.  Press UP or DOWN switch and ad-

just output to 0%.

2) SPAN:  Apply 100% input.  Slide the Zero/Span Selector 

to the top position.  Press UP or DOWN switch and adjust 

output to 100%.

3) Check ZERO adjustment again with 0% input.
4) The ZERO and SPAN adjustments are processed in a dig-

ital processor, and therefore they do not interact.  Howev-

er, if ZERO value is changed, repeat the above procedure 

1) – 3).

Содержание Mini-M M2XRP2

Страница 1: ...ents The equipment must be mounted inside a suitable fire enclosure Altitude up to 2000 meters The equipment must be mounted inside a panel Risk of Electrical Shock The front cover of the panel is to be opened only by qualified service personnel The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE UL requirements Failure to observe...

Страница 2: ...e the body from the base socket DIN Rail 35mm wide Spring Loaded DIN Rail Adaptor DIN RAIL MOUNTING Set the base socket so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of base socket on the DIN rail and push in the lower When removing the socket push down the DIN rail adaptor utilizing a minus screwdriver and pull WALL MOUNTING Refer to EXTERNAL DIMENSIONS TE...

Страница 3: ...ch will not be lost even when you turn off power supply to the unit Zero and span are respectively set to 0 and 100 at the factory UP DOWN Switches The front cover cannot be opened to 180 deg when flush with neighboring units Configurator Jack FRONT VIEW with cover open LEFT SIDE VIEW with cover rem Input Monitor LED PL1 Input Monitor LED PL2 Status Indicator LED Zero Span Selector Top SPAN Middle...

Страница 4: ...ation 12V DC 5V DC Detect Level 2V 1V DETECTING LEVEL When the parameters have been set with DIP switches and the PC Configurator Software model JXCON a specific sensitivity scale is applied according to the pulse amplitude setting The scaled input voltage is then compared to the preset detecting level 2 00 to 4 00V With DC coupling the scaled maximum voltage must be higher than the detecting leve...

Страница 5: ...shown in the table below The accuracy may not be assured if no filter is applied FREQUENCY RANGE NOISE FILTER TYPE 0 10 mHz With 0 100 mHz With 0 1 Hz With 0 10 Hz W O 0 100 Hz W O 0 1 kHz W O 0 10 kHz W O 0 100 kHz W O Output Type OUTPUT TYPE SW4 4 SW4 3 SW4 2 SW4 1 0 20 mA DC OFF ON OFF OFF 2 5 2 5 V DC ON OFF OFF ON 10 10 V DC ON OFF ON OFF STATUS INDICATOR LED The M2XRP2 is provided with a sta...

Отзывы: