background image

M2UDS

EM-5046  Rev.11  P. 3 / 3

MG CO., LTD. www.mgco.jp

5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

WIRING INSTRUCTIONS

 

SCREW TERMINAL

Torque: 0.8 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 100% input and adjust output to 0%.
2) SPAN:  Apply 0% input and adjust output to 100%.
3) Check ZERO adjustment again with 100% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 100%, 
75%, 50%, 25% and 0% input signal.  Check that the output 
signal for the respective input signal shows 0%, 25%, 50%, 
75% and 100% within accuracy described in the data sheet.  
When the output is out of tolerance, recalibrate the unit ac-
cording to the “ADJUSTMENT PROCEDURE” explained 
earlier.

LIGHTNING SURGE PROTECTION

We offer a series of lightning surge protector for protec-
tion against induced lightning surges.  Please contact us to 
choose appropriate models.

Отзывы: