EM-5076  Rev.8  P. 2 / 4

 

FILTER

• The M2PRU is designed to accept at the maximum of 100 

kHz, which may cause errors due to chattering in the in-
put pulses.

   A filter circuitry (time constant: approx. 1 msec.) is in-

corporated to eliminate unwanted chattering when the 
mechanical contact input is specified.  It is effective for 
most relay types, however, an external CR filter as indi-
cated below, could be added if the user need improvement.  
Limit the input frequency to 10 Hz at maximum.

C

+

Relay

R

PULSE

SCALER

C = 100 µF
R = 100Ω

COMPONENT IDENTIFICATION

Model

Body

Base Socket

Pulse Sensing
Type Selector

Connection

Diagram

Specifications

Fixing Screw

INSTALLATION

Loosen the fixing screw at the front of the unit in order to 
separate the body from the base socket.

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

 

DIN RAIL MOUNTING

Set the base socket so that 
its DIN rail adaptor is at 
the bottom.  Position the 
upper hook at the rear side 
of base socket on the DIN 
rail and push in the lower.  
When removing the socket, 
push down the DIN rail 
adaptor utilizing a minus 
screwdriver and pull.

 

WALL MOUNTING

Refer to “EXTERNAL DIMENSIONS.”

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

5

9

21.5 (.85)

70.5 (2.78)

86.7 (3.41)

7.3 (.29)

15 (.59)

6 (.23)

59 (2.32)

DIN RAIL

35mm wide

[4 (.16)]

8–M3

SCREW

72 (2.83)

23 (.91)

2–4.2x5

(.17x.20)

MTG HOLE

6 (.24) deep

116.7 (4.59)

• When mounting, no extra space is needed between units.

1

4

8

12
14 13

4 (.16)

Содержание Mini-M M2PRU

Страница 1: ...lass of this unit satisfies the system requirements Altitude up to 2000 meters The equipment must be mounted inside a panel The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE UL requirements Failure to observe these requirements may invalidate the CE UL conformance The actual installation environments such as panel con figuration...

Страница 2: ...tor Connection Diagram Specifications Fixing Screw INSTALLATION Loosen the fixing screw at the front of the unit in order to separate the body from the base socket DIN Rail 35mm wide Spring Loaded DIN Rail Adaptor DIN RAIL MOUNTING Set the base socket so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of base socket on the DIN rail and push in the lower When rem...

Страница 3: ...les 9 12 9 12 Voltage Pulse 9 12 AC DC SWITCH 12kΩ 24V 1 4 5 1 4 5 Capacitor Coupled PWR 1 4 5 2 Wire Current Pulse Built in Excitation 1 5 4 Vsns 2 WIRE PICK UP External DC Supply 1 5 4 Vsns 2 WIRE PICK UP DC SUPPLY 200Ω 200Ω WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 8 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicab...

Страница 4: ...Min 400 µsec recommended for AC DC switch output of which the internal voltage drop value may increase with a shorter pulse width OFF H ON L OUTPUT TYPE Bold section of the waveform is adjustable VOLTAGE PULSE OPEN COLLECTOR AC DC SWITCH PULSE WIDTH RANGE Selects adjustable range of the output pulse width L Left Approx 0 2 10 msec CTR Center Approx 5 200 µsec R Right Approx 10 400 msec PULSE SENSI...

Отзывы: