MAINTENANCE

Check M-RESTER periodically. Many cases of lightning are 
ignored, and even lightning at a far distance often causes 
inductive surges.
We recommend that you check your M-RESTER about twice 
a year, before and after the rainy season. Check whenever 
you experience a strong lightning occurrence.
Checking procedure is explained in the following:

 

CHECKING

WIRING

• Make sure that wiring is done as instructed in the con-

nection diagram.

• Make sure that the Ground terminal (G) is connected to 

the metallic housing of protected equipment.

• Make sure that the Ground terminal (G) is grounded to 

earth.

POWER PILOT LAMP

• Supply appropriate AC voltage through the M-RESTER 

and check the LEDs. When the LED is off despite that 
power is supplied, replace the M-RESTER.

DISCHARGE FUNCTION

Turn off the power supply and remove all wiring connected 
to MRESTER before testing its discharge capability as fol-
lows:

• Check resistance across the following terminals on the 

high resistance range of multimeter (infinite standard).

MH-1201, MH-2201: Terminals U-W, U-G, W-G
MH-2203: Terminals U-V, U-W, U-G, V-W, V-G, W-G

• Check that discharging occurs across the same terminals 

with a 500V DC megger. (Indicator of the megger reaches 
over-scale.)

• If any of the above tests shows negative, replace the M-

RESTER.