BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Surge protector (Head e Base)  ........................... (1)
DIN rail mounting adaptor* .............................................. (1)
Screws for DIN rail mounting (M4 × 8)* .......................... (2)
*Included with option code /A33
(Base section is optional.)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERAL

 

FUNCTION & FEATURES

• Designed specifically for 4 – 20mA DC and pulse signal 

line including both 4-wire and 2-wire transmitters

• Life monitor function helps you to decide when you 

should replace the surge protector; reduces maintenance 
and prevents downtime

• Pressing CHK (Check) button confirms the degradation 

and life span of the surge protection circuits with LEDs

• Absorbs surges only without affecting instrumentation signal
• No interruption of signal by unplugging surge protector element

 

SPECIFICATIONS

LINE TO LINE

LINE TO

EARTH

MDPA-24

MDPA-65

Max. continuous
operating voltage (Uc)

30V

70V

±160V

Voltage protection level
(Up) @1kV (100A)

45V

85V

±650V

Voltage protection level
(Up) @2kV (1kA)

50V

100V

±650V

Leakage current
(new device)

≤ 5µA

@30V DC

≤ 5µA

@70V DC

≤ 5µA

@±140V DC

Capacitance @1 MHz

≤ 1000 pF ≤ 1000 pF

≤ 100 pF

Response time

≤ 4 nsec.

≤ 4 nsec.

≤ 20 nsec.

Max. line voltage

30V

70V

----

Max. discharge current (Imax)

5000A (8 / 20 µs)

Nominal current (I

N

)

100mA

Internal series resistance

20 Ω ±10% including return

POINTS OF CAUTION

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the surge protector inside proper housing with 
sufficient ventilation.

• Do not install the surge protector where it is subjected to 

continuous vibration.  Do not subject the unit to physical 
impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 30 to 85% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind the surge protector’s cables together with 

those in which noises are present.  Do not install them in 
the same duct.

 

DIELECTRIC STRENGTH TEST

• Loosen the screw located at the left-center of the element 

and remove the element module from the base before 
conducting a dielectric strength testing.  Otherwise the 
element will start discharging at a voltage exceeding the 
max. continuous operating voltage (Uc), which can cause 
insulation failure of the module.

   Be sure to return the element and fasten securely after 

the test.

 

BATTERY LIFE

• The battery’s life is assured for 10 years from the manu-

facturing date indicated at the right-top of the specifica-
tion label (when used ≤ 2 minutes/month).

• The battery continues to discharge even while it is un-

used.  We recommend not to store the Element module for 
a long period of time.

 

AND ....

• We recommend that you keep spare surge protectors so 

that you can replace them when necessary.

• Lightning surge can enter not only through signal lines 

but also through power supply lines.  We recommend that 
you also use the surge protectors for power line for suffi-
cient protection.