ALARM INDICATOR LED

The front LEDs turn ON when the power is supplied, and 
OFF in an abnormality.
When one or more LEDs are OFF, check the following:

1) Measure voltage across the power supply terminals with 

a multimeter.

2) When DC power supply is confirmed, replace the M-

RESTER with a new one.

3) When the voltage is 0V, supply appropriate DC voltage 

and check the LEDs. If one or more LEDs are OFF, re-
place the MRESTER with a new one.

MAINTENANCE

Check M-RESTER periodically. Many cases of lightning are 
ignored, and even lightning at a far distance often causes 
inductive surges.
Even with the alarm indicator LEDs on the MDH unit, we 
recommend that you check your M-RESTER about twice a 
year, before and after the rainy season. Check whenever you 
experience a strong lightning occurrence.
Checking procedure is explained in the following:

 

CHECKING

WIRING

• Make sure that wiring is done as instructed in the con-

nection diagram.

• Make sure that the Ground terminal (2, 3, 6 or 7) is con-

nected to the metallic housing of protected equipment.

• Make sure that the Ground terminal (2, 3, 6 or 7) is 

grounded to earth.

 

DISCHARGE FUNCTION

Remove all the wires before testing its discharge capability 
as follows:

• Check resistance across the terminals indicated below. 

(Indicator of the tester shows ≥10MΩ.)

          (1) – (8), (1) – (2), (8) – (2)

• Check that discharging occurs across the same terminals 

with a 500V DC megger. (Indicator of the megger shows 
≤20MΩ.)

• If any of the above tests shows negative, replace the whole 

MRESTER unit.