INSTALLATION

Detach the yellow clamps located at the top and bottom of the unit for separating the body from the base socket.

 

DIN RAIL MOUNTING

Set the base socket so that its DIN rail adapter is at the bottom. Hung the upper hook at the rear side of base socket on the 
DIN rail and push in the lower. When removing the socket, push down the DIN rail adapter utilizing screwdriver (–) and pull.

Clamp

(top & bottom)

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

Shape and size of the base socket are
slightly different with various socket types. 

 

WALL MOUNTING

Refer to the drawings below

 

EXTERNAL DIMENSIONS mm [inch]

3

4

5

6

2

1

8

7

80 [3.1

5]

50 [1.97]

103 [4.06]

123 [4.84]

(3.3 [.13])

80 [3.1

5]

20 [.79]

40 [1.57]

50 [1.97]

7.8 [.31]

CLAMP

(top & bottom)

DIN RAIL

35mm wide

2

4.5 [.18] dia.

MTG HOLE

15 [.59] deep

8

M3.5

SCREW

• When mounting, no extra space is needed between units.

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.
Be sure to cross-wire between the Ground terminal (2 or 7) and metallic housing of the protected equipment. (100Ω max.)

4

7

5

1

8

OUTPUT

INPUT

M-RESTER

P+

G

P–

+

+

+

S+

S–

G

Lightning Arrester

for Signal Line

Cable

DC POWER

Protected

Equipment

Ground one of the terminals 2, 3, 6 and 7.

+

 

GROUNDING

M-RESTER

PROTECTED

EQUIPMENT

G

G

CROSSOVER WIRE

GROUNDING

(100 ohms or less)

A crossover wire between M-RESTER ground and the ground or 

metallic housing of the equipment is required for protection.

If the protected equipment has no ground terminal, ground the 

M-RESTER only.

MDH

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8169  Rev.5  P. 2 / 3