BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Lightning surge protector (body + base socket)  ................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTALLATION / INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, and basic main-
tenance procedure.

LIMITATION APPLICABLE TO M-RESTER

The M-Rester will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-Rester may not be effective against certain 
extremely high voltages caused by a direct or almost di-
rect hit by lightning.
M-Rester must be installed according to this installa-
tion/ instruction manual.

GENERAL

 

FUNCTION & FEATURES

• Designed specifically for DC power supplies up to 5 amps
• Discharge current capacity 2000A
• Absorbs surges only without affecting instrumentation 

signal

• Indicator LEDs ON with surge absorber failure
• Fuse provided for detaching the discharge elements

 

SPECIFICATIONS

BETWEEN LINES

LINE TO GND

MDH-12

MDH-24

MDH-48

Discharge voltage 24V min. 50V min. 88V min. ±380V min
Max. surge voltage* 70V max. 140V max. 210V max. ±700V max.
Leakage current 

≤15mA

@15V DC

≤15mA

@30V DC

≤20mA

@70V DC

≤1mA

@±380V DC

Response time

≤0.1 µsec.

Discharge current

2000A (8 / 20 µsec.)

Max. load current

5A

Voltage drop

≤1V

*The maximum voltage that could pass through M-RESTER. 
Protected equipment must be able to withstand this voltage 
for a very short time period.

POINTS OF CAUTION

 

ENVIRONMENT

• When heavy dust or metal particles are present in the 

atmosphere,

install M-RESTER inside proper housing and ventilate it.

• Do not install the M-RESTER where it is subjected to 

continuous

vibration. Do not apply physical impact to the M-RESTER.

• Environmental temperature must be within -5 to +55°C 

in order to

ensure adequate life span and operation.

 

WIRING

• Remove cables connected to the ground terminals (2, 3, 6 

or 7) from the base socket before conducting a dielectric 
strength test.  Otherwise the element will start discharg-
ing at discharge voltage, which can cause insulation fail-
ure. Be sure to return the cables as they were after the 
testing is complete.

 

RATED CURRENT

• Be sure that the rated current of protected equipment 

does not exceed the maximum load current specification 
of the M-RESTER.

• Be sure to install a breaker which matches the current 

rating at the power source side of the M-RESTER.

COMPONENT IDENTIFICATION

Body

Base Socket

Specification

Label

 

FRONT PANEL CONFIGURATION

Alarm LED (two)

LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY USE

(DC power use)

MODEL

MDH

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8169  Rev.5  P. 1 / 3

INSTRUCTION MANUAL