![background image](http://html1.mh-extra.com/html/m-system/mdcat-a-series/mdcat-a-series_instruction-manual_3155026002.webp)
MDCAT-A
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8165 Rev.0 P. 2 / 4
INSTALLATION
Mount the unit on a DIN rail. Once installed, do not move it to another DIN rail.
■
MOUNTING THE UNIT ON A DIN RAIL
A) Hang the upper hook of the DIN rail mounting adaptor at
the rear side of unit, on the DIN rail.
B) Push in the lower in keeping pressing the unit to the DIN
rail.
DIN Rail
B
A
■
REMOVING THE UNIT
A) Pull down the DIN rail adaptor utilizing a minus screw-
driver.
B) Pull out the lower part of the unit.
C) Detach the upper part from the DIN rail.
C
B
A
DIN rail adaptor
GENERAL
■
FUNCTION & FEATURES
• Designed specifically for Ethernet network
• Conforms with 1000 Base-T, PoE and PoE Plus
• LAN cable’s shield wire can be floating or grounding by a shortcircuit bar
• Pressing CHK (Check) button confirms with LEDs the life span of the surge protect device
• DIN rail mounting
■
SPECIFICATIONS
LINE TO LINE (pair)
LINE
TO
LINE (PoE)
LINE
TO
EARTH
MDCAT-A-5E
MDCAT-A-6
Max. continuous operating voltage (Uc)
±6V
±3.3V
±58V
±150V
Voltage protection level (Up)
±15V @2kV
±10V @2kV
±100V @2kV
±600V @4kV
Leakage current @Uc
25µA
5µA
25µA
5µA
Max. discharge current (Imax)
100A
100A
100A
10kA
Nominal current (I
N
)
1A
Series resistance
Approx. 0Ω
Insertion loss
≤ 3dB
Transmission performance: TIA/EIA-568-B.2
CAT5e
(MDCAT-A-5E)
CAT6
(MDCAT-A-6)