M-system MD7PM Скачать руководство пользователя страница 4

MD7PM

EM-8055  Rev.3  P. 4 / 4

 

CONNECTION DIAGRAM

M-RESTER

6

3

8

5

2

(SHLD)

DIN RAIL

DIN RAIL

ADAPTOR

Protected Device

FG

Protected Side

Crossover Wire

Surge Side

*

1. Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground.  

 

Use a steel or copper rail.

*

2. Be sure to ground the DIN rail.  Recommended grounding resistance ≤100Ω

*

3. Cross-wire between the DIN rail and the metal housing of the protected device to equalize the earth potential.  

 

Ground only the surge protector when the protected device has no ground terminal.

*

4. Shield wiring method is an example.  Proceed according to the system requirements.

*

4

*

2

*

3

Crossover Wire

*

3

7

M-RESTER

POT

3

6

7

5

DIN RAIL

DIN RAIL

ADAPTOR

Surge Side

Protected Side

Metal Enclosure

*

2

*

1

*

1

8

SG

INPUT

+

4

1

1

4

+

max.

min.

max.

min.

2

WIRING INSTRUCTIONS

 

EURO TERMINAL 

Torque: 0.3 N·m
Applicable wire size: 0.2 – 2.5 mm

2

Stripped length: 8 mm

MAINTENANCE

Check surge protectors periodically.  Many cases of light-
ning are ignored, and even lightning at a far distance often 
causes inductive surges.
We recommend that you check your surge protector about 
twice a year, before and after the rainy season.  Check 
whenever you experience a strong lightning occurrence.
Checking procedure is explained in the following:

 

CHECKING

WIRING

1) Make sure that wiring is done as instructed in the con-

nection diagram.

2) Make sure that the DIN rail is connected to the metal 

enclosure of protected device.

3) Make sure that the surge protector is securely attached 

to the DIN rail, and that the rail is grounded to earth.

DISCHARGE ELEMENT

1) Remove all wiring connected to the surge protector when 

you test the module.

2) Check resistance across the terminals indicated in Table 

2 on the high resistance range of multimeter and confirm 

no conduction.  The tester should show 10 MΩ or greater.

3) Confirm conduction across the same terminals with a 500 

V DC 1000 MΩ insulation tester.  The tester should show 

20 MΩ or less.

4) If any of the above tests shows negative, replace the 

surge protector.

Table 2.

TERM.          

MODEL

MD7PM-FF MD7PM-FG MD7PM-GF MD7PM-GG

4 – 5

Yes

Yes

Yes

Yes

4 – 6

Yes

Yes

Yes

Yes

5 – 6

Yes

Yes

Yes

Yes

4 – 8

No

Yes

Yes

Yes

5 – 8

No

Yes

Yes

Yes

6 – 8

No

Yes

Yes

Yes

8 – 6

No

No

Yes

Yes

6 – DIN rail

Yes

Yes

No

Yes

8 – DIN rail

Yes

No

Yes

No

Note 1:  Apply (+) voltage of the multimeter to the terminal 

number indicated on the left side.

Note 2: Polarity does not matter for the insulation tester.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание MD7PM

Страница 1: ...st of the surge voltages However M RESTER may not be effective against cer tain extremely high voltages caused by a direct or almost direct hit by lightning M RESTER must be installed according to this installa tion instruction manual GENERAL FUNCTION FEATURES High discharge current capacity 20 kA 8 20 µs 1 kA 10 350 µs Ultra thin 7 mm wide module can be mounted in high density Excellent protectio...

Страница 2: ... spare surge protectors so that you can replace them when necessary Lightning surge can enter not only through signal lines but also through power supply lines We recommend that you also use the Lightning Surge Protector for Power Lines for adequate protection COMPONENT IDENTIFICATION Body Spring Loader DIN Rail Mounting Adaptor for grounding Connection Diagram left side Model No Indication INSTAL...

Страница 3: ...1 2 3 7 4 1 5 2 6 3 8 7 95 3 74 7 28 98 3 86 1 5 06 8 M3 EURO TERMINAL DIN RAIL 35 mm wide DIN RAIL ADAPTOR WIRE INSERTION ANGLE approx 20 57 2 24 1 9 07 Figure 1 GROUNDING M RESTER PROTECTED EQUIPMENT FG CROSSOVER WIRE Cross wire from the DIN rail to the metal housing of the protected device to equalize the ground potential Ground only the surge protector when the protected device has no groundin...

Страница 4: ...nd after the rainy season Check whenever you experience a strong lightning occurrence Checking procedure is explained in the following CHECKING WIRING 1 Make sure that wiring is done as instructed in the con nection diagram 2 Make sure that the DIN rail is connected to the metal enclosure of protected device 3 Make sure that the surge protector is securely attached to the DIN rail and that the rai...

Отзывы: