M-system MD7PM Скачать руководство пользователя страница 2

MD7PM

EM-8055  Rev.3  P. 2 / 4

POINTS OF CAUTION

 

ENVIRONMENT

• 

Indoor use.

• 

When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.

• 

Do not install the unit where it is subjected to continuous
vibration.  Do not subject the unit to physical impact.

• 

Environmental temperature must be within -25 to +85°C
(-13 to +185°F) with relative humidity within 30 to 90%
RH in order to ensure adequate life span and operation.

• 

This unit needs a DIN rail as earth grounding bar.  Ox-
ide coating of an aluminium rail may lower the electric
conductivity between this module and the ground.  Use a
steel or copper rail.

 

DIELECTRIC STRENGTH TESTING

• 

The surge protector starts discharging when 160V or
greater voltage (with floating shield type) or several volts
(with grounding shield type) is applied between lines and
earth.  Remove the grounding wire before conducting a
test.  Be sure to return the wire after the test.

 

AND ....

• 

We recommend that you keep spare surge protectors so
that you can replace them when necessary.

• 

Lightning surge can enter not only through signal lines
but also through power supply lines.  We recommend that
you also use the Lightning Surge Protector for Power
Lines for adequate protection.

COMPONENT IDENTIFICATION

Body

Spring Loader

DIN Rail Mounting

Adaptor (for grounding)

Connection

Diagram

(left side)

Model No.

Indication

INSTALLATION

Mount the unit on a DIN rail.  Once installed, do not move 
it to another DIN rail.

 

MOUNTING THE UNIT ON A DIN RAIL

A) Hang the upper hook of the DIN rail mounting adaptor at 

the rear side of unit, on the DIN rail.

B) Push in the lower in keeping pressing the unit to the DIN 

rail.

C) DIN rails generally have slight individual variability in

size.  If you find it difficult to push in the lower part, go

back to (A) and hang the upper part more deeply onto the

rail and try (B) again.

A

DIN Rail

B

 

REMOVING THE UNIT

A) Push down the spring loader utilizing a minus screwdriv-

er.

B) Confirm that it is pulled enough down and pull out the

lower part of the unit.

C) Detach the upper part from the DIN rail.

A

B

Spring Loader

C

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание MD7PM

Страница 1: ...st of the surge voltages However M RESTER may not be effective against cer tain extremely high voltages caused by a direct or almost direct hit by lightning M RESTER must be installed according to this installa tion instruction manual GENERAL FUNCTION FEATURES High discharge current capacity 20 kA 8 20 µs 1 kA 10 350 µs Ultra thin 7 mm wide module can be mounted in high density Excellent protectio...

Страница 2: ... spare surge protectors so that you can replace them when necessary Lightning surge can enter not only through signal lines but also through power supply lines We recommend that you also use the Lightning Surge Protector for Power Lines for adequate protection COMPONENT IDENTIFICATION Body Spring Loader DIN Rail Mounting Adaptor for grounding Connection Diagram left side Model No Indication INSTAL...

Страница 3: ...1 2 3 7 4 1 5 2 6 3 8 7 95 3 74 7 28 98 3 86 1 5 06 8 M3 EURO TERMINAL DIN RAIL 35 mm wide DIN RAIL ADAPTOR WIRE INSERTION ANGLE approx 20 57 2 24 1 9 07 Figure 1 GROUNDING M RESTER PROTECTED EQUIPMENT FG CROSSOVER WIRE Cross wire from the DIN rail to the metal housing of the protected device to equalize the ground potential Ground only the surge protector when the protected device has no groundin...

Страница 4: ...nd after the rainy season Check whenever you experience a strong lightning occurrence Checking procedure is explained in the following CHECKING WIRING 1 Make sure that wiring is done as instructed in the con nection diagram 2 Make sure that the DIN rail is connected to the metal enclosure of protected device 3 Make sure that the surge protector is securely attached to the DIN rail and that the rai...

Отзывы: