background image

EM-8055  Rev.3  P. 1 / 4

INSTRUCTION MANUAL

LIGHTNING SURGE PROTECTOR FOR

POTENTIOMETER USE

 (ultra-slim)

MODEL

MD7PM

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Surge protector ....................................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
When using this product in potentially explosive atmos-
phere or hazardous (classified) location, you have to follow
the safety procedure to install it.  Please refer to “SAFE IN-
STALLATION MANUAL” for each type of certification.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERAL

 

FUNCTION & FEATURES

• 

High discharge current capacity 20 kA (8 / 20 µs), 1 kA
(10 / 350 µs)

• 

Ultra-thin 7-mm-wide module can be mounted in high
density

• 

Excellent protection employing multi-stage SPD circuits

• 

DIN rail mounting and grounding

• 

Shield terminal provided

 

SPECIFICATIONS

See Table 1.

Table 1. Specifications

MODEL NO.

MD7PM-FF

MD7PM-FG

MD7PM-GF

MD7PM-GG

Max. continuous operating voltage (Uc)

Line to Line

7.5V

Line to Earth

±160V

±7.5V

Line to SHLD

±160V

±7.5V

SHLD to Earth

±160V

short

±160V

short

Voltage protection level (Up)

Line to Line

25V

@4kV (1.2 / 50 µs)

Line to Earth

±800V

±25V

Line to SHLD

±1200V

±800V

±25V

SHLD to Earth

±800V

short

±800V

short

Leakage current @Uc

Line to Line

≤5µA

Other sections

≤5µA

Response time

Line to Line

≤4 nsec.

Other sections

≤20 nsec.

Max. discharge current (Imax)

20kA (8 / 20 µs), 1.0kA (10 / 350 µs)

Nominal current (I

N

)

100mA

Internal series resistance

4.7Ω ±10% per line

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание MD7PM

Страница 1: ...st of the surge voltages However M RESTER may not be effective against cer tain extremely high voltages caused by a direct or almost direct hit by lightning M RESTER must be installed according to this installa tion instruction manual GENERAL FUNCTION FEATURES High discharge current capacity 20 kA 8 20 µs 1 kA 10 350 µs Ultra thin 7 mm wide module can be mounted in high density Excellent protectio...

Страница 2: ... spare surge protectors so that you can replace them when necessary Lightning surge can enter not only through signal lines but also through power supply lines We recommend that you also use the Lightning Surge Protector for Power Lines for adequate protection COMPONENT IDENTIFICATION Body Spring Loader DIN Rail Mounting Adaptor for grounding Connection Diagram left side Model No Indication INSTAL...

Страница 3: ...1 2 3 7 4 1 5 2 6 3 8 7 95 3 74 7 28 98 3 86 1 5 06 8 M3 EURO TERMINAL DIN RAIL 35 mm wide DIN RAIL ADAPTOR WIRE INSERTION ANGLE approx 20 57 2 24 1 9 07 Figure 1 GROUNDING M RESTER PROTECTED EQUIPMENT FG CROSSOVER WIRE Cross wire from the DIN rail to the metal housing of the protected device to equalize the ground potential Ground only the surge protector when the protected device has no groundin...

Страница 4: ...nd after the rainy season Check whenever you experience a strong lightning occurrence Checking procedure is explained in the following CHECKING WIRING 1 Make sure that wiring is done as instructed in the con nection diagram 2 Make sure that the DIN rail is connected to the metal enclosure of protected device 3 Make sure that the surge protector is securely attached to the DIN rail and that the rai...

Отзывы: