manualshive.com logo in svg
background image

WIRING

 

LEADWIRES

Conductor cross-section area: 8 to 35 mm

2

 (stripped length 

15 mm) for both the power and the ground lines.  14 mm

2

 

minimum is recommended.

 

TORQUE

Tighten the screw terminals securely.  Recommended torque 
is of 4.5 N·m.

 

MARKING LABEL

Use the marking labels included in the product package to 
identify power lines.  The labels are appropriate in size to be 
placed close to each terminal as designated in the external 
dimensions.
Nine labels are printed with typical markings.

L1

L2

L3

N

E

G

PE

PEN

 

WIRING BRIDGE

Wiring bridges for two units (model: CNB2-4), for three 
units (model: CNB2-5) and for four units (model: CNB2-7) 
are available for easy cross-wiring to the ground. 

 

WIRE LENGTH

Keep the wire length to the minimum for both the power 
source side and the ground side.  Connect the surge protec-
tor and the protected device to the same equipotential bond-
ing bar as following.  The wire length between the branch 
point and the ground should ideally be less than 0.5 meters. 

Equipotential bonding bar

a

b

a+b ≤ 0.5 m

SPD

Power

GROUNDING

 

COMMON GROUNDING WITH CROSS-OVER WIRE

Basically a common grounding with cross-wiring between 
the MAL and the protected device is recommended for ad-
equate protection.  Ground both the surge protector and the 
protected device to the same equipotentially bonding bar as 
following.  If the protected device has no ground terminal, 
ground only the MAL.

Protected

Device

G

N

ACC

SPD1 SPD1 SPD2

Equipotential bonding bar

SPD1: MAL
SPD2: MALN
ACC: CNB2

 

Single-phase/3-wire connection (TT system)

Circuit

Breaker

 

INSTALLING THE DEVICES SEPARATELY

When installing the surge protector in a low-voltage inlet, 
grounding is likely to be independent if the protected device 
is not installed nearby.  In this case, potential difference 
between the surge protector and the protected device less-
ens lightning protection function when thunder storming.  
When the wiring distance from the surge protector is 10 
m or more, maximum surge voltage becomes high potential 
due to reflection.  When the wiring distance exceeds 10 m, 
install the other class II surge protection near the protected 
device as following.

Protected

Device

G

N

ACC1

SPD1 SPD1 SPD2

Equipotential bonding bar

SPD1: MAL
SPD2: MALN
ACC1: CNB2

SPD3: MAKF
SPD4: MAKN
ACC2: CNB

 

Single-phase/-wire connection (TT system)

ACC2

Service entrance switch gear

SPD3

SPD3

SPD4

≥ 10 m

Circuit

Breaker

Circuit

Breaker

MAL

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8162  Rev.1  P. 7 / 8

Содержание MAL-230x

Страница 1: ...device such as a lightning rod and low voltage electronics equipment are connect ed with equipotential bonding 2 In case the low voltage wiring is possible to be hit by the direct or almost direct li...

Страница 2: ...ution board 10 m or more away from the low voltage inlet energy coordination is achieved FEATURES CURRENT CAPACITY The one port SPD can be used regardless of the load cur rent SAFETY AND HIGH DENSITY...

Страница 3: ...CNB2 CIRCUIT CONNECTION DIAGRAM Thermal Breaker L N PE 1 2 Discharge Element ALARM OUTPUT Terminal block provided for the alarm output option Schematic shows the operation in normal conditions INSTALL...

Страница 4: ...he data sheets of the class II surge protector for details 4 If the service entrance switchgear and switchgear or protective device wiring distance is more than 10 m install the class II surge protect...

Страница 5: ...re star connection Protected device G L2 L1 L1 L2 L3 L3 N N SPD2 ACC SPD1 SPD1 Protected device SPD2 G L2 L1 L3 ACC SPD1 SPD1 POWER e g SPD1 MAL 400A Three phase 4 wire 220V AC MAL 230x SPD2 ACC CNB2...

Страница 6: ...g SPD1 Three phase 4 wire 220V AC MAL 230x SPD2 MALN 230 ACC CNB2 7 ACC SPD1 SPD1 SPD1 Protected device G L1 L2 L3 ACC SPD1 SPD1 SPD1 N L1 L2 L3 1 Wiring only for three phase 4 wire Generator or trans...

Страница 7: ...evice is recommended for ad equate protection Ground both the surge protector and the protected device to the same equipotentially bonding bar as following If the protected device has no ground termin...

Страница 8: ...peri ence a strong lightning storm DO NOT attempt checking or replacing the surge protector during a thunder storm for safety Checking procedure is as explained below CUTTING OFF POWER SUPPLY Cut off...

Отзывы: