manualshive.com logo in svg
background image

 

CONNECTION DIAGRAM

+

+

AC

POWER

UNIT

4

5

FG

3

U

V

AC POWER

FG

3

2

1

+

+

■ 

DC Power Supply

■ 

AC Power Supply

OUTPUT 1

OUTPUT 1

Ch.1

OUTPUT

Ch.8

OUTPUT

OUTPUT 1

OUTPUT 1

+

+

OUTPUT 2

OUTPUT 2

Ch.1

OUTPUT

+

+

OUTPUT 2

OUTPUT 2

Ch.8

OUTPUT

POWER

+

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the power ter-

minals.

3) Installation & environment

MAINTENANCE

Power units’ standard life is expected for 10 years with 
average ambient temperature 35°C (95°F) and 1.0A load.  
Contact M-System for use in extremely different conditions.

 

HOW TO REPLACE THE POWER UNIT (power input code: M2)

1) Prepare Power Unit (switching regulator) model HDC10.
2) Turn off the power supply connected to the Power Unit.
3) Remove the wire binding and wiring connected to the ter-

minal 1 – 2 and 4 – 5.

4) Loosen and remove the mounting screws A (4 places).
5) Detach the Power Unit from the Installation Base.
6) Attach the new Power Unit to the Installation Base and 

tighten the screws in reverse order as explained above.

Note:  For questions on products purchased before 2009, please 

contact M-System.

A: Mounting screws with

washer, M3 x 6 (4 pls.)

1: 24 V DC (+)
2: 24 V DC (-)
3: FG
4: AC power input (U)
5: AC power input (V)

3
4
5

2

1

V.ADJ

A

A

A

A

M8BS2-082

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5479-2  Rev.5  P. 3 / 3