16 samples and 32 samples, and press Set button.
3) Press Mode button to save the setting and exit the Mov-
ing Average setting.
HYSTERESIS (DEADBAND)
1) Choose Hysteresis from the Set Up Transmitter and
press Set button.
2) Use Up-Down buttons to choose L1 deadband within the
display scale range and press Set button.
3) Use Up-Down buttons to choose L2 through L4 in the
same manner. Pressing Set button shifts the cursor posi-
tion to a next point.
4) Press Mode button to save the setting and exit the Hys-
teresis setting.
ALARM LATCHING
An alarm with latching option does not automatically reset
once the alarm is tripped, until the setting is enabled, or the
power supply is turned off and on.
1) Choose Latching from the Set Up Transmitter and press
Set button.
2) Use Up-Down buttons to choose Enable or Disable and
press Set button.
3) Press Mode button to save the setting and exit the Alarm
Latching setting.
■
LCD SETTING MODE
Press Mode button for at least 2 seconds to show the Con-
tents and choose LCD Mode, and press Set button.
Once in the LCD Mode, you can move from one parameter to
another by pressing Mode button briefly.
When all the setting is complete, press the Mode button for
at least 2 seconds to return to the Monitor Mode.
DISPLAY CONTRAST
1) Choose Contrast from the LCD Mode and press Set but-
ton.
2) Use Up-Down buttons to choose an appropriate contrast
in %. Alternatively, press Set button to set the contrast
to 50%.
3) Press Mode button to save the setting and exit the Con-
trast setting.
DISPLAY BACKLIGHT
1) Choose Back Light from the LCD Mode and press Set
button.
2) Use Up-Down buttons to choose either On, Off, or Off
Timer and press Set button.
3) If Off Timer is selected, specify also a time before the
backlight is off from 1 to 3600 seconds.
4) Press Mode button to save the setting and exit the Back
Light setting.
Whatever is this setting, a red backlight is maintained
while the unit is in alarm conditions.
■
INFORMATION MODE
Press Mode button for at least 2 seconds to show the Con-
tents and choose Information, and press Set button.
Once in the Information, you can move from one parameter
to another by pressing Mode button briefly.
When all the setting is complete, press the Mode button for
at least 2 seconds to return to the Monitor Mode.
PROPERTY
This menu is for display purpose only.
1) Choose Property from the Information and press Set but-
ton.
2) Model, Firmware version, Serial and Tag numbers are
shown.
3) Press Mode button to exit the Property.
TAG NUMBER (NAME)
1) Choose Tag No. from the Information and press Set but-
ton.
2) Use Up-Down buttons to choose a first character and
press Set button to confirm and shift the cursor to a next
position. A second character can be entered in the same
manner, up to 10 characters.
3) Press Mode button to save the setting and exit the Tag
No. setting.
■
ALARM TEST MODE
The output relays can be manually turned on and off with-
out applying input signals for testing purposes. While in
this mode, the actual input signal does not affect the output
relay operation.
1) Press Mode button for at least 2 seconds to show the Con-
tents and choose Alarm Test, and press Set button.
2) Press Set button one or more times to shift the cursor
position to the alarm point for which you want to conduct
testing.
3) Use Up-Down buttons to switch the relay on and off.
4) Press Set button to go to other alarm points and test in
the same manner.
5) Press the Mode button for at least 2 seconds to return to