background image

MODEL: M5PA

Waveform:  Square or sine
Input impedance: ≥ 10 kΩ
Max. voltage between input terminals: ±50 V
Detecting H level
5 V pulse: ≥ 3 V
12 V, 24 V pulse: ≥ 6 V
Detecting L level
5 V pulse: ≤ 1 V
12 V, 24 V pulse: ≤ 4 V

OUTPUT SPECIFICATIONS

■ DC Current: 0 – 20 mA DC
  Minimum span: 1 mA
  Offset: Max. 1.5 times span
  Load resistance: Output drive 11 V max.
■ DC Voltage: 0 – 10 V DC
  Minimum span: 1 V
  Offset: Max. 1.5 times span
  Load resistance: Output drive 10 mA max.; at ≥ 1 V

INSTALLATION

Power Consumption
•AC:
  Approx. 2 VA at 100 V
  Approx. 3 VA at 200 V
  Approx. 3 VA at 264 V
•DC: Approx. 2 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 0 to 90 %RH (non-condensing)
Mounting: DIN rail
Weight: 80 g (2.8 oz)

PERFORMANCE in percentage of span

Accuracy: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: Max. 0.5 sec. + 1 pulse cycle (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength (input to output to power to ground)
  DC powered: 2000 V AC @1 minute
  AC powered: 1500 V AC @1 minute

STANDARDS & APPROVALS

CE conformity:
EMC Directive (2004/108/EC)
  EMI EN 61000-6-4: 2007
  EMS EN 61000-6-2: 2005

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com