background image

M3LU2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

EM-2653-A  P. 6 / 8

  4 ) 100% Input Ranging: Apply the desired maximum 

input level (e.g. 5V) from the simulator and push UP 

button until the LD1 blinks for approx. 2 sec. and then 

turns OFF.  When you release the button, the LD1 is 

returned to ON.

  5 ) Output Configuration Mode: Push MODE button and 

confirm that the LD3 red LED instead of LD2 is blink-

ing.

  6 ) 0% Output Ranging: Increase or decrease the simu-

lated input until the meter shows the desired mini-

mum output level (e.g. 1V).  Push DOWN button until 

the LD1 blinks for approx. 2 sec. and then turns OFF.  

When you release the button, the LD1 is returned to 

ON.

  7 ) 100% Output Ranging: Increase or decrease the 

simulated input until the meter shows the desired 

maximum output level (e.g. 5V).  Push UP button until 

the LD1 blinks for approx. 2 sec. and then turns OFF.  

When you release the button, the LD1 is returned to 

ON.

  8 ) Run Mode: Programming complete, push MODE 

button and confirm that only the LD1 green LED is 

blinking.

 

I/O RANGE LABEL

Blank I/O range labels are included in the product package.  
Write in the configured ranges and put the label on the side 
as shown below.

INPUT
OUTPUT

I/O Range Label (included in the product package)

 

HOW TO RESET TO DEFAULT STATUS

  1 ) Set and SW2-1 to OFF and SW2-2 to ON position.
  2 ) Turn on the power supply to the transmitter while 

pressing MODE button.

  3 ) Wait until green light turns on at the LD1, LD2 and 

LD3.

  4 ) Reset SW2-1 and SW2-2 to the previous position.  Turn 

off and on the power supply.

 

CALIBRATION FLOW CHART

POWER ON

Amber LED

Green LED

Control
Buttons

Red LED

OFF

ON

Blink

RUN MODE

LD2

LD3

A

G

RUN MODE

LD2

LD3

G

R

LD1

LD2

LD3

LD1

LD2

LD3

0% INPUT

CONFIGURED

100% INPUT

CONFIGURED

INPUT

CALIBRATION

MODE

LD1

OUTPUT

CALIBRATION

MODE

LD2

LD3

LD1

LD2

LD3

0% OUTPUT

CONFIGURED

100% OUTPUT

CONFIGURED

G

G

R

R

R

R

G

R

R

G

Fine Adjustments ?

I/O Ranging ?

PUSH  

MODE

 

 1 – 2 s

PRESS & HOLD  

MODE

 

 > 5s

PUSH  

MODE

PUSH  

MODE

PUSH  

MODE

PUSH  

MODE

PUSH

DOWN

PUSH

UP

DOWN

UP

MODE

PUSH

DOWN

PUSH

UP

When you set 0% or 100% input/output ranges, 
keep pressing UP or DOWN button until the
LD1 blinks for approx. 2 seconds and turns off, 
which indicates the setup is complete.
When you release the button, the LD1 is returned
to ON.

*

For the model M3LU2-x/A, the green LED is blinking.  

For the model M3LU2-x/B, the green LED turns on.

FINE ZERO

CALIBRATION MODE

UP

  or  

DOWN

FINE SPAN

CALIBRATION MODE

UP

  or  

DOWN

Apply simulated 0% input signal.

Apply simulated 100% input signal.

Adjust simulated input until the output meter 
shows desired 0% output.

Adjust simulated input until the output meter 
shows desired 100% output.

LD1

*

LD1

*

Содержание M3LU2

Страница 1: ...unit satisfies the system requirements Altitude up to 2000 meters The equipment must be mounted inside a panel The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional pr...

Страница 2: ...mponents from damage DO NOT pull beyond where the housing cover is latched The plastic housing may be damaged HOW TO SEPARATE THE TERMINAL BLOCKS When you need to separate the terminal blocks from the transmitter body for wiring insert a minus driver between the terminal block and the housing body pull up the driver and pull out the terminal block INSTALLATION DIN RAIL MOUNTING Set the unit so tha...

Страница 3: ...hat the AC power and DC power connect to different terminals AC POWERED TYPE B 1 3 2 4 5 6 CONFIGURATOR JACK 7 8 11 12 3 2 1 POT DC max min 2 wire RTD 3 wire RTD 4 wire RTD A A T C OUTPUT DC POWER B B A B A B VOLT mA mV CJC SENSOR ext wire DC POWERED TYPE V U B A A B B A B A B WIRING INSTRUCTIONS Applicable wire size Solid 0 2 to 2 5 mm2 0 55 to 1 75 dia Stranded 0 2 to 2 5 mm2 Tinning wire ends m...

Страница 4: ...er supply removed Selectable I O type and ranges are listed in Table 12 and 13 DIP SW CONFIGURATION MODE Turn the SW3 8 OFF to enable the DIP SW Field Configu ration mode as shown in Table 1 See Table 3 through 9 to configure the input and Table 10 for the output PC CONFIGURATION MODE Turn the SW3 8 ON to enable the PC Configuration mode as shown in Table 1 All programmable features can be set up ...

Страница 5: ...extension wires or lead wires of mV input are broken the output goes over 100 below 0 with downscale protection due to burnout function Confirm the status indicator LED pattern and check leadwires in such a case 5 Output Check that the load resistance meets the described specifications I O RANGING FINE ADJUSTMENTS After the DIP SW setting is complete set up the precise input and output range using...

Страница 6: ...UT I O Range Label included in the product package HOW TO RESET TO DEFAULT STATUS 1 Set and SW2 1 to OFF and SW2 2 to ON position 2 Turn on the power supply to the transmitter while pressing MODE button 3 Wait until green light turns on at the LD1 LD2 and LD3 4 Reset SW2 1 and SW2 2 to the previous position Turn off and on the power supply CALIBRATION FLOW CHART POWER ON Amber LED Green LED Contro...

Страница 7: ...ONFORMANCE RANGE ACCURACY 1 PR K CA E CRC 20 20 20 0 to 1760 270 to 1370 270 to 1000 0 to 1760 150 to 1370 170 to 1000 1 00 0 25 0 20 36 36 36 32 to 3200 454 to 2498 454 to 1832 32 to 3200 238 to 2498 274 to 1832 1 80 0 45 0 36 J IC T CC B RH 20 20 20 210 to 1200 270 to 400 100 to 1820 180 to 1200 170 to 400 400 to 1760 0 25 0 25 0 75 36 36 36 346 to 2192 454 to 752 212 to 3308 292 to 2192 274 to ...

Страница 8: ...MODE System Error Indicates the CPU s communication error DIP SW Error DIP SW configuration is inappropriate Check the DIP SW setting referring to Tables 2 11 Burnout in PC Configuration Mode Option A Burnout in DIP SW Configuration Mode PC Configuration RUN Mode Option A The transmitter is configured via PC and is in normal operating conditions DIP SW Configuration RUN Mode The transmitter is con...

Отзывы: