MODEL: M2PRU

most relay types, however, an external CR filter as indicated
below, could be added if the user need improvement.  Limit
the input frequency to 10 Hz at maximum.

Relay

R

C

PULSE

SCALER

C = 100 µF
R = 100

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Chattering protection: Filter provided for mechanical
contact input (time constant: approx. 1 msec.)
Input pulse sensing: DC coupled; capacitor coupling
(automatic trigger*) is field selectable with the side DIP
switch for the voltage pulse input.
*Capacitor coupling, with which the detecting levels are
automatically set within two peaks of the waveforms, is
effective way to detect those with DC offset.  However, it
may be ineffective if the duty ratio is extremely high or low.
The automatic trigger method can compensate such
irregular pulses.
Scaling factor adjustment: 10-position rotary switch (front);
1.0000 × 10

0

 – 0.0001 × 10

–6

; factory set to 1.0000 × 10

if

not specified when ordering
Output pulse width adjustment: Single-turn screwdriver
adjustment (front); 5 μsec. – 400 msec. (one-shot type);
Factory set to 5 μsec. except for the mechanical contact
input set to 15 msec. or AC/DC switch output set to 500
μsec.
(Min. 400 μsec. recommended for AC/DC switch output of
which the internal voltage drop value may increase with a
shorter pulse width.)
Output pulse width range selector: Double-throw SW (front)

INPUT SPECIFICATIONS

Excitation: Shortcircuit protection; limited to approx. 40 mA
at shortcircuit
• Open Collector
Frequency range: 0 – 100 kHz
Pulse width time requirement: Min. 5 μsec. for ON and OFF
Sensing: Approx. 24 V DC @2 mA
Detecting levels: ≤ 400 Ω / 0.8 V for ON,
≥ 1200 Ω / 2.4 V for OFF
• Mechanical Contact
Frequency range: 0 – 30 Hz
Pulse width time requirement: Min. 10 msec. for ON and OFF
Sensing: Approx. 24 V DC @2 mA
Detecting levels: ≤ 400 Ω / 0.8 V for ON,

≥ 1200 Ω / 2.4 V for OFF
• Voltage Pulse
Waveform: Square or sine
Frequency range: 0 – 100 kHz
(min. 10 Hz for sine waves)
Pulse width time requirement: ≥ 5 μsec. for high and low
levels
Input impedance: ≥ 10 kΩ
Max. input voltage across the terminals: ±50 V
Detecting levels
DC coupled: ≥ 2 V DC for high level; ≤ 1 V DC for low level
Capacitor coupled: ≥ 2 Vp-p
• Two-wire Current Pulse
Frequency range: 0 – 100 kHz
Pulse width time requirement: Min. 5 μsec. for high and low
levels
Detecting levels:
≥ 10 mA for high level
≤ 5 mA for low level
Maximum current: ±30 mA
Input resistance: Receiving resistor 200 Ω

OUTPUT SPECIFICATIONS

• Open Collector: 50 V DC @200 mA (resistive load)
Maximum frequency: 100 kHz
Saturation voltage: 0.6 V DC
• Voltage Pulse
Maximum frequency: 100 kHz
High level: Rating (5, 12 or 24 V) ±10 %
Low level: ≤ 0.5 V
Load resistance:
≥ 500 Ω for 5 V
≥ 1200 Ω for 12 V
≥ 4800 Ω for 24 V
• AC/DC Switch:
132 V AC @200 mA (cos ø = 1)
30 V DC @200 mA (resistive load)
Maximum frequency: 1 kHz
Internal voltage drop: ≤ 3 V

INSTALLATION

Power Consumption
•AC Power input:
 Approx. 4 VA at 100 V
 Approx. 5 VA at 200 V
 Approx. 6 VA at 264 V
•DC Power input: Approx. 3 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lbs)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание M2PRU

Страница 1: ...z 90 264 V for UL DC Power R 24 V DC Operational voltage range 24 V 10 ripple 10 p p max R2 11 27 V DC Operational voltage range 11 27 V ripple 10 p p max Select N for Standards Approvals code P 110 V...

Страница 2: ...shortcircuit Open Collector Frequency range 0 100 kHz Pulse width time requirement Min 5 sec for ON and OFF Sensing Approx 24 V DC 2 mA Detecting levels 400 0 8 V for ON 1200 2 4 V for OFF Mechanical...

Страница 3: ...t Reinforced insulation Approval UL C UL nonincendive Class I Division 2 Groups A B C and D hazardous locations ANSI ISA 12 12 01 CAN CSA C22 2 No 213 UL C UL general safety requirements UL 61010B 1 C...

Страница 4: ...or Input Connection Examples PWR Voltage Pulse DC Coupled PWR Open Collector Output Connection Examples 9 12 9 12 Voltage Pulse 9 12 AC DC SWITCH SCALING FACTOR ADJ Scaler PULSE WIDTH ADJ 12k 24V 1 4...

Страница 5: ...o observe these re quirements may invalidate the CE UL conformance POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicat...

Страница 6: ...in the diagram below or refer to the connection diagram on the side of the unit OUTPUT 9 12 U V POWER 13 14 INPUT 1 5 4 SENSOR EXCITATION Mechanical Contact Open Collector Input Connection Examples PW...

Страница 7: ...switches 10 1 through 10 n apply respectively to each digit of the decimals and exponential as shown below Output Rate Input Rate 0 A B C D 10 E where the scaling factor is adjustable from 1 0000 10...