POWER ON

Amber LED

Green LED

Control

Buttons

Red LED

OFF

ON

Blink

RUN MODE

LD1

LD2

LD3

A

G

RUN MODE

LD1

LD2

LD3

G

R

LD1

LD2

LD3

LD1

LD2

LD3

0% INPUT

CONFIGURED

100% INPUT

CONFIGURED

INPUT

CALIBRATION

MODE

LD1

OUTPUT

CALIBRATION

MODE

LD2

LD3

LD1

LD2

LD3

0% OUTPUT

CONFIGURED

100% OUTPUT

CONFIGURED

G

G

R

R

R

R

G

R

R

G

Fine Adjustments ?

I/O Ranging ?

PUSH  

MODE

 

 1 – 2 s

PRESS & HOLD  

MODE

 

 > 5s

PUSH  

MODE

PUSH  

MODE

PUSH  

MODE

PUSH  

MODE

PUSH

DOWN

PUSH

UP

DOWN

UP

MODE

PUSH

DOWN

PUSH

UP

When you set 0% or 100% input/output ranges, 

keep pressing UP or DOWN button until the

LD1 flashes for approx. 2 seconds and turns off, 

which indicates the setup is complete.

When you release the button, the LD1 is returned

to ON.

If the LED does not change, the entered level may

be inappropriate: e.g. out of usable range.

FINE ZERO

CALIBRATION MODE

UP

  or  

DOWN

FINE SPAN

CALIBRATION MODE

UP

  or  

DOWN

Apply simulated 0% input signal.

Apply simulated 100% input signal.

Adjust simulated input until the output meter 

shows desired 0% output.

Adjust simulated input until the output meter 

shows desired 100% output.

Once the transmitter

enters the fine zero

calibration mode, 

the output goes to 

preadjusted 0% 

value regardless 

of the present input 

signal.

Once the transmitter

enters the fine span

calibration mode, 

the output goes to 

preadjusted 100% 

value regardless 

of the present input 

signal.

 CALIBRATION FLOW CHART