background image

M2LPM

P.  / 6

EM-5054-A Rev.2

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  DIP SW setting:  Check that the switches are set to ap-

propriate positions.

3)  Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

4)  Input:  Check that the input signal is within 0 – 100% of 

full-scale.

  If  the  potentiometer  wires  are  broken,  the  output  goes 

over  100%  (below  0%  with  downscale  burnout)  due  to 
burnout function.  Confirm the status indicator LED pat-
tern and check leadwires in such a case.

5)  Output:    Check  that  the  load  resistance  meets  the  de-

scribed specifications.

I/O RANGING & FINE ADJUSTMENTS

After  the  DIP  SW  setting  is  complete,  set  up  the  precise 
input and output range using the front control buttons.
The  front  LEDs’  colors  and  flashing  patterns  help  you  to 
easily identify the transmitter’s status and confirm the set-
up actions in each step of Calibration Modes.  Please read 
the  following  explanations  referring  to  “Calibration  Flow 
Chart” in the next page.

 PREPARATION (e.g. Input 0 – 500Ω, Output 1 – 5V)

1)  Mount the DIP-SW-configured M2LPM on to a DIN rail.
2)  Connect  the  M2LPM  to  a  simulator  and  a  multimeter 

and to a DC power source as shown below.

3)  Turn the power supply on and wait for 10 minutes.

 INPUT & OUTPUT RANGING

[Example]
1)  Run  Mode:  Confirm  that  the  LD1  green  light  is  blink-

ing.

2)  Input Configuration Mode: Press MODE button for long-

er than 5 seconds until the LD1 red light is ON and the 
LD2 red light is blinking.

3)  0%  Input  Ranging:  Apply  the  desired  minimum  input 

level (e.g. 0Ω) from the potentiometer and push DOWN 
button until the LD1 flashes for approx. 2 sec. and then 
turns OFF.  When you release the button, the LD1 is re-
turned to ON.  

  The flashing LD1 means that the value is stored in the 

memory.  If the LED does not change, the entered level 
may be inappropriate:  too small a span, or out of usable 
range (same for all steps).

4)  100% Input Ranging: Apply the desired maximum input 

level  (e.g.  500Ω)  from  the  potentiometer  and  push  UP 
button until the LD1 flashes for approx. 2 sec. and then 
turns OFF.  When you release the button, the LD1 is re-
turned to ON.

5)  Output  Configuration  Mode:  Push  MODE  button  and 

confirm that the LD3 red light instead of LD2 is blink-
ing.

6)  0% Output Ranging: Increase or decrease the simulated 

input until the meter shows the desired minimum out-
put  level  (e.g.  1V).    Push  DOWN  button  until  the  LD1 
flashes for approx. 2 sec. and then turns OFF.  When you 
release the button, the LD1 is returned to ON.

7)  100%  Output  Ranging:  Increase  or  decrease  the  simu-

lated input until the meter shows the desired maximum 
output  level  (e.g.  5V).    Push  UP  button  until  the  LD1 
flashes for approx. 2 sec. and then turns OFF.  When you 
release the button, the LD1 is returned to ON.

8)  Run Mode: Programming complete, push MODE button 

and confirm that only the LD1 green light is blinking.

 ZERO & SPAN ADJUSTMENTS

After the transmitter is installed and operational, fine zero 
and span tuning can be performed as explained below.  Both 
zero and span are adjustable within ±15%.
1)  Run  Mode:  Confirm  that  the  LD1  green  light  is  blink-

ing.

2)  Fine Zero Calibration Mode: Press MODE button for 1 

or 2 seconds until the LD1 red light is ON and the LD2 
green light is blinking.

3)  Use UP (increase) and DOWN (decrease) buttons to ad-

just the output to 0%.

4)  Fine  Span  Calibration  Mode:  Push  MODE  button  and 

confirm that the LD3 green light instead of LD2 is blink-
ing.

5)  Use UP (increase) and DOWN (decrease) buttons to ad-

just the output to 100%.

6)  Run Mode: Push MODE button and confirm that only the 

LD1 green light is blinking.

Note 1: Calibration steps can be skipped when not needed 
by repeating pushing MODE buttons.
Note  2: There  is  no  stated  order  of  setting  0%  and  100% 
levels or no limitation of entering values for multiple times 
within one step of Calibration Mode.  Signal level is stored 
each time the respective UP or DOWN button is pressed.

1
8

9

12
13

14

M2LPM

Multimeter

+

AC Power Source

5

+

3

2

1

POTENTIOMETER

max.

min.

Отзывы: