Automatic test following E DIN EN 63027 

 

In the background an automatic test for the unit is performed about every 24h. 
A pseudo-arc is generated in the toroid coil and processed by the circuitry. If there is 
no fault in the circuitry, an alarm (red LED)will not be generated and the test remains 
undetected. In case of a fault, the LED (Image 1: Pos. 4) shines red , the plug socket 
(Image 1, Pos 2) is no longer energized and the mains control lamp is off . If a reset or 
calibration (see chapter 5. and 6. ) are not successful, the unit needs to be returned 
to the manufacturer. 
 
 
 

5.

 

Reset 

 

By pressing the green push-button „Reset“(Image 1, Pos. 7) for 2 seconds after the 
LED went red because of an arc detection, the red LED will shine green again if there 
is no other fault in the circuitry. Pushing the red and green push-buttons (Image 1, 
Pos. 6+7 ) simultaneously for 2-4 seconds a calibration is performed (see chapter 6.)  
 
 
 
 

6.

 

Calibration 

 

If there is a disturbance on the cable to be monitored and the red LED is on (Image 1, 
Pos. 4) and if the red LED will not shine green after reset (see chapter 5.), there will 
be a fault in the sensor´s circuitry or the voltage created by the disturbance is outside 
the calibration range. In this case you press simultaneously the “Test” push-button 
(Image 1, Pos.6) and the “Reset” push-button (Image 1, Pos. 7) for 2-4 seconds. The 
circuitry automatically adjusts itself to the new voltage. After that, a self-test is 
performed. If this test is positive, the green LED will be on again as well as the mains 
control lamp (Image 1, Pos. 1). Calibration can be performed at any time during 
normal operation. If the LED stays red after calibration, please pull the cable to be 
monitored out of the toroid coil and retry a calibration. If the LED goes green, the 
adapter cannot adjust itself to the specific disturbance on the cable to be monitored, 
arc detection will not be possible any more. If the LED stays red without the cable to 
be monitored, unplug the adapter from mains, unplug any switch-off unit from the 
plug-socket (Image 1, Pos. 2 ) and return the adapter to the manufacturer. 
 
 

7.

 

Cover Caps (Image 1, Pos. 3) 
 
There are two black cover caps on the surface of the adapter´s housing. 

Only the 

manufacturer is allowed to remove these caps. 

 
 
 
 
 

Содержание LiBo-8

Страница 1: ...ortant notice from the Manufacturer Article No 25630009 01 for 8 und 25630010 01 for 16 Image 1 LiBo Adapter with Toroid Coil 8 5 Housing with plug socket 2 Mains Control Lamp 1 Duo LED Red Green 4 Cover Caps 3 red Push button Test 6 green Push button Reset 7 Image 2 Mains plug 8 ...

Страница 2: ...apter 6 from this manual If there is a loss of mains power and mains comes back the LED Image 1 Pos 4 will be red for a short period of time Mains control lamp Image 1 Pos 1 is off and finally change to the status prior to mains loss Alarm Red or normal operation Green If the mains control lamp Image 1 Pos 1 is on the plug socket Image 1 Pos 2 is energized 2 Duo LED Red Green Image 1 Pos 4 This LE...

Страница 3: ... if the red LED will not shine green after reset see chapter 5 there will be a fault in the sensor s circuitry or the voltage created by the disturbance is outside the calibration range In this case you press simultaneously the Test push button Image 1 Pos 6 and the Reset push button Image 1 Pos 7 for 2 4 seconds The circuitry automatically adjusts itself to the new voltage After that a self test ...

Страница 4: ...r Image 3 Pos 1 The cover of the fuse holder needs to be removed upwards carefully The fuse will be taken out of the holder carefully be checked and replaced eventually After that the cover of the fuse holder will be reinstalled Attention Replace the fuse by same typ and electric parameters Upon request the adapter can be delivered with different fuse parameters which are corresponding to the load...

Страница 5: ...cm Direct current of the cable to be monitored Toroid coil 8 minimum of 50A Toroid coil 16 minimum of 100A higher currents upon request Plug socket output for loads mains switched to plug socket by DPST relay Protection Earth PE of plug connected to PE of plug socket Factory made fuse 5x20mm 0 4A slow blow inside the housing Attention please read carefully chapter 8 for safety advices Galvanic iso...

Страница 6: ...s Caused by a variety of disturbances on DC cables a calibration might not be successful for a proper operation of the adapter Before placing an order the manufacturer presumes the test of an adapter on loan and for a certain amount of time to make sure the adapter is working properly in the application of the customer Warranty corresponding to the General Terms and Conditions of the manufacturer ...

Страница 7: ...7 Der Partner in Sachen Elektronik Königsberger Str 8 85368 Moosburg Tel 0 87 61 72 54 0 Fax 0 87 61 72 54 27 Email info m system gmbh de www m system gmbh de Moosburg October 7th 2019 ...

Отзывы: