LC / LCS

P. 4 / 4

EM-1355 Rev.3

SIMPLE LOOP TEST OUTPUT

  Option /E2

Simulated 0% and 100% output is available with Option /E2.
Switch the Loop Test Selector positions.

Top position:

0% fixed

Middle position: 100% fixed
Bottom position: Cancel the loop test mode

(Back to the normal operating mode)

CHECKING

1) Terminal wiring:  Check that all cables are correctly

connected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 7

– 8 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

■ 

FRONT PANEL CONFIGURATION

• Option /E

• Option /E2

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty.  To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

LCD Meter

Span Adj.

Zero Adj.

Excitation Adj.

Loop Test Selector

Top
Middle
Bottom

: 0% fixed
: 100% fixed
: Cancel
  (normal operating mode)

NEXT Key

ENTER Key

Span Adj.

Zero Adj.

Excitation Adj.

■ 

EXCITATION

This unit is calibrated at the factory for use with the rating
described on the specification label.  However if you need to
adjust it for use with a rating other than the factory setting,
refer to the equation below.

Excitation Voltage =

  5 [V] 

×

 a [mV/V]   

[V]

           b [mV/V]

     where

a : Rating described on specification label
b : Actual rating

With 350

 bridge resistance, the excitation can be adjusted

from 2V to 10V.
When the result of above calculation exceeds 10V, adjust the
excitation to 10V.

■ 

ZERO (TARE) ADJUSTMENT

Adjustable from 0 to 80% of the input span (strain gauge
rating).  With no load applied, turn the Zero Adjustment until
the output shows 0%.

■ 

SPAN (SENSITIVITY) ADJUSTMENT

Adjustable from 20 to 100% of the input span (strain gauge
rating).  With the full-scale load, turn the Span Adjustment
until the output shows 100%.

MAINTENANCE

Regular calibration procedure is explained below:

■ 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%,
50%, 75% and 100% input signal.  Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of
tolerance, recalibrate the unit according to the "ADJUST-
MENT PROCEDURE" explained earlier.