M-system KDA3 Скачать руководство пользователя страница 2

KDA3

P. 2 / 5

EM-3646 Rev.2

FRONT PANEL CONFIGURATION & PROGRAMMING WITH PU-2

• Response Messages

OK: OK
NG: No good.  Check modular jack connection.
ER: Communication error

26-pin Connector

(Pin Assignments)

1

2

25

26

Modular Jack

G

ITEM No.

I

(

)

D

Response Messages

Data to be entered
or Messages

LCD Display

MDF.

CODE

ITEM

INPUT DATA

EXAMPLE (DEFAULT)

CONTENTS

01

S

0, 1

MNTSW : MON MODE

Modification code
0 : Data indication only.
1 : All parameters are modifiable.

02

D

STATUS : 0

Status indication

03

D

Output type

DEVICE : 0

0 : V1

DEVICE : 1

1 : V2

DEVICE : 2

2 : Z1

04

P

0 – 99

POWONDELAY : 5

Power ON-delay time (seconds)

10

D

-15.0 – 115.0

%PV : XXX.X

Output indicated in % (as set in ITEM 26/27)

11

P

-99.99 – 99.99

ZERO : 0.00

Zero adjustment (%) (fine adj. of the value set in ITEM 26)

12

P

-99.99 – 99.99

SPAN : 0.00

Span adjustment (%) (fine adj. of the value set in ITEM 27)

13

D

PV : YYYY

Output indicated in engineering unit (as scaled in ITEM 14/15)

14

P

-9999 – 9999

SCALE 0 : -9999

BCD

Scaled range     0% *

1

15

P

-9999 – 9999

SCALE 1000 : 9999

Scaled range 100% *

1

14

P

-7FFF – 7FFF

SCALE 0 : -7FFF

Binary

Scaled range     0% *

1

15

P

-7FFF – 7FFF

SCALE 100 : 7FFF

Scaled range 100% *

1

14

P

0000 – FFFF

SCALE 0 : 0000

Offset binary

Scaled range     0% *

1

15

P

0000 – FFFF

SCALE 100 : FFFF

Reflected binary

Scaled range 100% *

1

14

P

8000 – 7FFF

SCALE 0 : 8000

Two's complement

Scaled range     0% *

1

15

P

8000 – 7FFF

SCALE 100 : 7FFF

Scaled range 100% *

1

17

P

0, 1, 2, 3, 4

CODE : 0

Input code

0 : BCD with polarity (decimal)
1 : Binary with polarity
2 : Offset binary
3 : Two’s complement
4 : Relfected binary

18

P

0, 1, 2, 3, 4

AV1L_BIT : 0

Available number of bits
0: 16 bits      1: 14 bits       2: 12 bits       3: 10 bits       4: 8 bits

19

P

0, 1

POLAR : 1

POL input

0 : Unavailable (not used)
1 : Available (used)

20

P

0, 1

DATA_LOGIC : 1

Data input logic*

2

0 : Positive
1 : Negative

21

P

0, 1, 2

LOAD_LOGIC : 0

LOAD input

0 : LOAD at Low or shortcircuit*

3

1 : LOAD at High or opencircuit*

4

2 : Unavailable (not used)

22

P

0, 1

POLAR_LOGIC : 1

POL input

0 : Negative at High or opencircuit*

4

1 : Negative at Low or shortcircuit*

3

23

P

0, 1, 2

PARITY : 0

Parity check

0 : Disable
1 : Enable Parity per each digit
2 : Enable Parity for all digits

24

P

0, 1

PARITY_TYPE : 0

Odd or even parity

0 : Odd
1 : Even

25

P

0.0 – 60.0

LAG_TIME : 0.0

Delay buffer (seconds, 0 – 90%)
When the Response Time model suffix code is specified to 1, the set
value is only effective at 5.0 or higher value.