![M-system JPR2 Скачать руководство пользователя страница 8](http://html.mh-extra.com/html/m-system/jpr2/jpr2_instruction-manual_683673008.webp)
JPR2
P. 8 / 8
EM-580 Rev.2
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this
warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
SOFTWARE SETTING
Please refer to the Operation Manual for Model PU-2x (EM-9255), Section B: (B-1) Introduction, (B-2) General Operation
Description, (B-3) Operation Flowchart for general information.
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3) Check the input signal.
4) Check the output signal.
[GROUP 01]
ITEM
MDF.
INPUT DATA EXAMPLE (EXAMPLE) DEFAULT CONTENTS
CODE
01
S
N/A
MAINTENANCE SWITCH
0
MTSW : MON.MODE
0 : Data indication only.
1
MTSW : PRG.MODE
1 : All ‘P’ marked parameters are modifiable.
02
P
Alphanumeric TG : XXXXXXXXXX
N/A
Tag name entry (10 characters max.)
03
P
Numeric
CNT : XXXXXX
0
Total input pulses (any count selectable)
04
P
Numeric
IN : XXXXXX
1
Input pulse set count (1 to 1 000 000)
05
P
Numeric
OUT : XXXXXX
1
Output pulse set count (1 to 1 000 000)
06
P
Numeric (Hz) FRQ : XXXX.XHz
10.0
Max. output frequency limit (0.5 to 100000.0 Hz)
07
P
Numeric (s) SMP : X.XXs
0.10
Sampling time (0.01 to 100.00 s)
08
D
No input
N/A
Input specification selected with the front rotary switch
SW : IN_V 1/20
SW = 0, Voltage input, Sensitivity scale = 1/20
SW : IN_V 1/10
SW = 1, Voltage input, Sensitivity scale = 1/10
SW : IN_V 1/5
SW = 2, Voltage input, Sensitivity scale = 1/5
SW : IN_V 1/2
SW = 3, Voltage input, Sensitivity scale = 1/2
SW : IN_V 1/1
SW = 4, Voltage input, Sensitivity scale = 1/1
SW : IN_V 5/1
SW = 5, Voltage input, Sensitivity scale = 5/1
SW : IN_V 10/1
SW = 6, Voltage input, Sensitivity scale = 10/1
SW : IN_OC, mA
SW = 7, Open collector, mechanical contact or two-wire
current input
SW : no use
SW = 8, (not used)
SW : no use
SW = 9, (not used)
SW : IN_RS422
DIP switch set to RS-422 line driver pulse
09
P
*
Count mode
*Factory default depends upon other specifications.
0
IN_EDGE : 0
Count at pulse rise
1
IN_EDGE : 1
Count at pulse sink
Modification Code
D : No modification (writing) possible. Used only for monitoring (reading).
S : Modifiable at any time.
P : Modifiable only when the MAINTENANCE SWITCH is in the ‘PRG’ mode.
ROM Version Indication
[GROUP 00] [ITEM 99]