manualshive.com logo in svg
background image

JPR2

P.  / 8

EM-580 Rev.2

EXPLANATIONS OF TERMS & FUNCTIONS

 SCALING FACTOR, INPUT PULSE SET COUNT & OUT-

PUT PULSE SET COUNT

The scaling factor, rate of number of output pulses divided 
by  number  of  input  pulses,  is  determined  by  two  param-
eters:  input pulse set count and output pulse set count.
The JPR2 output is designed to be proportional in number 
of pulses relative to the input.  For example, when the pulse 
rate is set to 0.0583, the JPR2, provided with 10000 input 
pulses, outputs 583 pulses.  However, the output is not sup-
plied in a constant frequency.  The JPR2 counts the number 
of input pulses during the sampling time (period) and stores 
it in the internal buffer counter, and provides the number 
of  output  pulses  multiplied  by  the  scaling  factor  for  the 
number of input pulses, by the end of next sampling cycle.  
With the maximum output frequency limit, those pulses ex-
ceeding the limit are still in the buffer and output only in 
the following cycle.

 SAMPLING TIME

The sampling time is defined as a time period required by 
the JPR2 to count the input signals for one cycle.  With its 
factory  default  setting  (0.1  sec.),  the  output  is  refreshed 
every 100 milliseconds.
This setting is not usually be changed unless for a specific 
purpose.

 MAXIMUM OUTPUT FREQUENCY LIMIT

You  can  limit  the  maximum  output  frequency  from  the 
JPR2.
The JPR2 multiplies the number of input pulses by the scal-
ing factor.  However when the output pulses are supplied to 
a low-speed response counter, the number of output pulses 
(output frequency of the JPR2) may have to be limited with-
in a certain level.
Those surplus pulses remains in the buffer and are output 
in the following sampling cycles within the limit.

 OPERATION

[Example]

Input frequency: 2 Hz
Sampling time: 0.5 sec.
Pulse rate: 3/2
Output pulse width: Duty ratio approx. 50%
Max. output frequency: 1 kHz

1)  The JPR2 counts the number of pulses during the sam-

pling time (period).  In the example, 1 count in 0.5 sec. 
time.

2)  Converts the number in the preset rate.  In the example, 

1 pulse 

×

 3/2 = 1.5 pulses

3)  Outputs the converted pulses in the next sampling pe-

riod.  If certain pulses are not output within the time due 
to a fraction or the max. output frequency limit, they are 
output in the following sampling period.  In the example, 
1  pulse  is  output  in  the  second  period,  two  pulses  are 
output in the third to adjust the fraction.

Содержание JPR2

Страница 1: ...MENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 60 C 23 to 140 F with relative humidity within 30 to 90 RH in order to ensure adequate life span an...

Страница 2: ...nal DC Supply 3 5 4 Vsns 2 WIRE PICK UP DC SUPPLY n Voltage Pulse 3 5 4 Vsns PWR n RS 422 Line Driver Pulse Vsns PWR n Open Collector Output Connection Examples 1 2 n Voltage Pulse 1 2 n Noncontact AC DC Switch AC Powered 1 n RS 422 Line Driver Pulse 2 LOAD Relay or Counter Coil Varistor or Spark Quenching Circuit DC Powered 1 2 LOAD Relay or Counter Coil Spark Quenching Diode 6 3 5 4 2 1 n OPEN C...

Страница 3: ...e With its factory default setting 0 1 sec the output is refreshed every 100 milliseconds This setting is not usually be changed unless for a specific purpose MAXIMUM OUTPUT FREQUENCY LIMIT You can limit the maximum output frequency from the JPR2 The JPR2 multiplies the number of input pulses by the scal ing factor However when the output pulses are supplied to a low speed response counter the num...

Страница 4: ...pen Collector or Noncontact AC DC Switch INPUT WAVEFORM H H L H H L L H L OFF ON L L H One shot detecting input pulse drop H L No pulse width conversion One shot detecting input pulse rise Inverted H H L H H L L L L H One shot detecting input pulse drop OFF ON No pulse width conversion One shot detecting input pulse rise Non Inverted OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON O...

Страница 5: ...nput High setting is recommend ed to prevent typical chattering from counting CAUTION FOR RS 422 LINE DRIVER PULSE For RS 422 line driver pulse the input amplitude detect ing level and noise filter settings are all invalid However in order to prevent errors in setting set these switches as follows Input amplitude 50 100 Vp p SW 0 Detecting level 0V Noise filter None INPUT TYPE SW1 1 2 3 4 5 6 Open...

Страница 6: ...1 DC Offset V 2 Sensitivity Scale Adjust the detecting level to the value calculated above following the procedure explained below Adjust the detecting level appropriate for the sensor excitation voltage Adjust the detecting level to 0V appropriate for RS 422 line driver pulse input Voltage pulse input or 2 wire current pulse input No No Yes Open collector input Yes 1 Rounded off to one decimal pl...

Страница 7: ...h the sensor excitation adj located behind the front cover If you need to change it check that the required current is within the specification How to Change the Excitation A voltmeter and ammeter of class 0 5 or better accuracy are required 1 Connect the voltmeter across the terminals 5 4 2 Connect the ammeter to terminal 5 3 Turn the potentiometer until the meter shows the de sired value Check t...

Страница 8: ...Power input voltage Check voltage across the terminal 7 8 with a multimeter 3 Check the input signal 4 Check the output signal GROUP 01 ITEM MDF INPUT DATA EXAMPLE EXAMPLE DEFAULT CONTENTS CODE 01 S N A MAINTENANCE SWITCH 0 MTSW MON MODE 0 Data indication only 1 MTSW PRG MODE 1 All P marked parameters are modifiable 02 P Alphanumeric TG XXXXXXXXXX N A Tag name entry 10 characters max 03 P Numeric ...

Отзывы: