• How to Change the Detecting Level

5

4

3

2

1

0

9

8

7

6

1

2

3

4

5

6

ON

Detecting Level Adj.

Detecting Level Adj. Pin

Input Monitor LED PL1

V

Connect to Terminal 6

of the base socket.

Voltmeter

For the capacitor coupling, turn the detecting level adjust-
ment fully counter-clockwise so that the detecting level is 
set to 0V.
For the DC coupling, refer to the procedure below.  A volt-
meter of class 0.5 or better accuracy with pointed probes is 
required.

1) Connect the negative probe of voltmeter to the terminal 6 

of base socket.

2) If you need a noise filter, set the SW4 and SW5 in ad-

vance.

3) Connect the positive probe to the test pin and turn the 

Detecting Level Adjustment until the meter shows de-

sired value.

4) Apply input signals and check that input monitor LED 

(PL1) blinks according to the input signal.

  If the LED does not blink, the detecting level may be out 

of pulse amplitude range.  Check the pulse amplitude 

and the DC offset again and readjust the detecting level.

 

SENSOR EXCITATION ADJUSTMENT

You can change the sensor excitation voltage with the sen-
sor excitation adj. located behind the front cover.  If you 
need to change it, check that the required current is within 
the specification.

+

OUTPUT

1

2

U(+)

V(–)

POWER

7

8

PU-2x

MODULAR JACK

INPUT

+ 5

4

6

+

SENSOR EXC.

9

10

ALARM OUTPUT

V

A

Ammeter

Voltmeter

• How to Change the Excitation

A voltmeter and ammeter of class 0.5 or better accuracy are 
required.

1) Connect the voltmeter across the terminals 4 – 6.
2) Connect the ammeter to terminal 4.
3) Turn the potentiometer until the meter shows the de-

sired value.

  Check that the current value indicated on the ammeter 

is within the allowable limit.  If the value is greater than 

the limit, lower the voltage value or connect a separate 

power source.  Otherwise, the transmitter may fail.

25

5

12

24

60

120

CURRENT (mA)

VOLTAGE (V)

Voltage (V) × Current (A)  ≤ 600mW

 

ANALOG OUTPUT ADJUSTMENT

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

• How to Calibrate The Output Signal

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 0% input and adjust output to 0%.
2) SPAN:  Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

JPA2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-1572  Rev.5  P. 6 / 9

Содержание JPA2

Страница 1: ...t in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environ...

Страница 2: ...ng no extra space is needed between units 3 9 4 CONNECTION DIAGRAM OUTPUT 1 2 U V POWER 7 8 PU 2x MODULAR JACK INPUT 5 4 6 SENSOR EXCITATION 9 10 ALARM OUTPUT 5 4 6 5k Dry Contact or Mechanical Contac...

Страница 3: ...pulse sink detected when it goes below the level input monitor LED OFF Two Wire Current Pulse The input resistor 100 converts the current signal 0 25mA into 0 2 5V A pulse rise detected when the volt...

Страница 4: ...with Amplitude 5V p p DC Offset 2 5V Frequency Range 0 1 kHz Input type Voltage Pulse Frequency range selected 0 1 kHz Select the frequency range and set 0 and 100 range values with the Programming Un...

Страница 5: ...collector Mechanical contact Two wire current pulse 1 A specific sensitivity scale is applied according to the pulse amplitude setting The scaled input voltage is then com pared to the preset detectin...

Страница 6: ...PU 2x MODULAR JACK INPUT 5 4 6 SENSOR EXC 9 10 ALARM OUTPUT V A Ammeter Voltmeter How to Change the Excitation A voltmeter and ammeter of class 0 5 or better accuracy are required 1 Connect the voltme...

Страница 7: ...5 Frequency Range 0 FRQRNG 10mHz 0 10 mHz 1 FRQRNG 100mHz 0 100 mHz 2 FRQRNG 1 0Hz 0 1 Hz 3 FRQRNG 10Hz 0 10 Hz 4 FRQRNG 100Hz 0 100 Hz 5 FRQRNG 1 0kHz 0 1 kHz 6 FRQRNG 10kHz 0 10 kHz 7 FRQRNG 100kHz...

Страница 8: ...ed pairs of I O points Refer to the figure below X nn Input Y nn Output Range 15 00 to 115 00 15 0 Y01 X02 X03 X04 X05 115 Y02 X01 Y03 Y04 100 Y05 INPUT OUTPUT 5 GROUP 01 ITEM MDFY DATA EXAMPLE 60 61...

Страница 9: ...rding to the connection diagram 2 Power input voltage Check voltage across the terminal 7 8 with a multimeter 3 Input Check that the input signal is within 0 100 of the full scale 4 Output Check that...

Отзывы: