background image

JC-CU

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

EM-9042 Rev.1  P. 1 / 6

HUB MODULE

( CUnet )

MODEL

JC-CU

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Hub module .........................................................................(1)
DIN rail mounter slider ......................................................(1)

 

MODEL NO.

Confirm that the model number described on the product is 
exactly what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside a panel.
• Use dual-shield cables (Shinko Seisen Industry Model 

ZHY262PBA) for the network. If it is not sufficient, use 
a ferrite core (TDK Model ZCAT3035-1330 or equivalent) 
for the network cable.

• Expose the shield at a part of the cable cover, clip it with a 

Loop clamp (Seiwa Electric Mfg. Model E08P03 or equiva-
lent), and ground it to the internal panel of the control 
panel.

• The actual installation environments such as panel con-

figurations, connected devices and connected wires may 
affect the protection level of this module when it is inte-
grated in a panel system.  The user may have to review 
the CE requirements in regard to the whole system and 
employ additional protective measures to ensure CE con-
formity.

 

POWER INPUT RATING & OPERATIONAL RANGE

Locate the power input rating marked on the product and 
confirm its operational range as indicated below:

24V DC rating: 24V ±10%
16−32V DC rating: 15−33V DC
Power consumtpion: 
JC-CU-3: approx. 0.9 W,  JC-CU-7: approx. 1.2 W

 

GENERAL PRECAUTIONS

Before you remove the module or mount it, turn off the 
power
supply and input signal for safety.

 

ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air, 

install the module inside proper housing with sufficient 
ventilation.

• Do not install the module where it is subjected to con-

tinuous vibration.  Do not subject the module to physical 
impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 10 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

The module is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for sat-
isfying complete performance described in the data sheet.

Содержание JC-CU

Страница 1: ...rations connected devices and connected wires may affect the protection level of this module when it is inte grated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure CE con formity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational rang...

Страница 2: ...6 LNK0 LNK5 LNK6 Status Indicator LED RJ 45 Modular Jack for Trunk Status Indicator LED RJ 45 Modular Jack for Feeder Power Supply Connector RJ 45 Modular Jack for Feeder Status Indicator LED Status Indicator LED PWR ERR ERR LED PWR LED SIDE VIEW SW1 ON SW1 1 2 3 4 Operating Mode Setting DIP SW SW1 Terminating Resistor Transfer Rate ON FRONT VIEW STATUS INDICATOR LED ID COLOR FUNCTION PWR Green ON...

Страница 3: ...TR 4 TR 5 NC 6 NC 7 NC 8 SLD Unused Unused Network Network Unused Unused Unused Shield Feeder CU1 CU2 CU3 CU4 CU5 CU6 1 NC 2 NC 3 TR 4 TR 5 NC 6 NC 7 NC 8 SLD Unused Unused Network Network Unused Unused Unused Shield Trunk CU0A CU0B COMMUNICATION CONNECTOR PIN ASSIGNMENT CODE 1 1 2 3 4 5 6 7 8 1 NC 2 NC 3 NC 4 TR 5 TR 6 NC 7 NC 8 SLD Unused Unused Unused Network Network Unused Unused Shield Feeder...

Страница 4: ...nting 1 Push down the DIN rail mounter slider with tip of a minus screwdriver 2 Pull the lower of the module 3 Remove the upper hook of the module from the DIN rail 1 2 3 SURFACE MOUNTING 1 Insert the DIN rail mounter slider until it clicks once as shown below 1 2 Mount the module with M4 screws referring the Exter nal Dimensions Torque 1 4 N m EXTERNAL DIMENSIONS module mm inch 50 1 97 3 12 115 4...

Страница 5: ...7 JC CU 7 11 1 2 3 1 2 3 FE PWR PWR POWER IN FE PWR PWR POWER OUT SLD NC NC NC TR TR NC NC CU0A COMMUNI CATION 1 2 4 3 6 5 8 7 SLD NC NC NC TR TR NC NC CU0B COMMUNI CATION 1 2 4 3 6 5 8 7 SLD NC NC NC TR TR NC NC SLD NC NC NC TR TR NC NC CU1 CU6 1 2 4 3 5 6 8 7 1 2 4 3 5 6 8 7 JC CU 3 12 SLD NC NC NC NC TR TR NC SLD NC NC NC NC TR TR NC CU0A COMMUNI CATION 1 2 4 3 6 5 8 7 CU0B COMMUNI CATION 1 2 4...

Страница 6: ...les at both end of the communication line The terminating resistor is incorporated in the feeder side port of the HUB module MOUNTING REQUIREMENTS module mm inch 125 4 92 CONFIGURATIONS The configurations such as communication mode and transfer rate must be same for all modules connected to the communication line The terminating resistor must be enabled for the mod ules at both end of the communic...

Отзывы: