3.7 I/O mapping setting
I/O mapping function is used to connect between specific inputs and outputs so that an input is copied as an
output in the remote location, for the purpose of multiplexing and telemetering.
I/O mapping for analog output
Signal connection is possible between AI and AO, DI and AO, MA and AO, and MD and AO.
Refer to [
] >
for detailed information.
I/O mapping for discrete output
Signal connection is possible between DI and DO, MD and DO, DI and GDO, and MD and GDO.
Refer to [
, and [
3.6.9 Grouped digital output (GDO)
] for detailed information.
NOTES
• Channels assigned for I/O mapping function cannot be controlled on the web browser or
used for alarm output. Any setting for the web browser control or the alarm output is invalid.
• MD and DO grouped in the GDO which is assigned for I/O mapping cannot be controlled
on the web browser or used for alarm output. Any setting for the web browser control or the
alarm output is invalid.
• Values applied for I/O mapping:
% (AI): Input values are applied as they are to the output.
Int, Uint (AI): Engineering unit values are applied to the output.
DI, MD: Current state is applied to the output.